3-29
PFC-6075 • 5403593 • Rev C • 2/13
CA-6075 Class A Expander Installation
The Class A configuration requires the use of the CA-6075. Once the card is installed, the additional terminals are provided for
the return loop of the NAC. The CA-6075 provides the terminals for both NACs, SLCs, and P-Link. Refer to the figures below for
examples of installing and wiring a Class A expander card.
Notes
:
One (1) CA-6075 Class A expander may be installed per panel.
1.
The CA-6075 provides the terminals for NACs, P-Link, and SLCs.
2.
Examples of Installing and Wiring a Class A Expander Card
Figure 29.
CA-6075
Class A Expander
#6-32 x 7/8 screws
5050793 bracket
#6-32 x 1/4 screws
guide pins
DWG #593-27
NAC 1 NAC 2
-
+ -
+
Notification
Appliance
NAC 1 NAC 2
-
+ -
+
DWG #602-5A