16
ID-E299-001GB
(alarm number zone number year—month-day)
The zone number informs about the alarm source and is consistent with the detection line number
(1…24).
The display shows the latest alarm number, number of the zone where the alarm occurred, and its
date. It is possible to read the alarm occurrence time with 1-second accuracy by pressing the
SELECTION push button; then in the date place the alarm time is displayed as shown below:
(alarm number line number hour-minute-second)
Pressing the SELECTION push button produces alternate display of the clock time and date.
Preceding alarms readout is possible with the counter ‘scrolling’ using the SET^ push bu[on. The
return to the latest alarm takes place after aborting the function by pressing the FUNCTION push
button and selection of the alarm counter readout function again.
5.3
CONTROL PANEL FUNCTIONS AT 3
RD
ACCESS LEVEL
It is possible to use the functions available at the 3
rd
access level after the control panel door opening
– Fig. 5. The P1-FUNCTION, P2-SELECTION, P3-SET^ and P4-SET` push bu[ons located inside the
control panel allows for the following functions application:
•
external signalling devices operation option setting,
•
general alarm signal transmission delay value setting,
•
event memory reset,
•
general alarm signal transmission delay disablement/re-enablement,
•
alarm variants programming,
•
relays programming.
A desired function recall is performed using the FUNCTION push button. The item that can be
modified is distinguished by the flashing tag. The tag location can be changed with the help of the
SELECTIONZ push bu[on. The selected value modi\ca]on is possible using the SET^ and SET`
push buttons.
5.3.1 Alarming lines (signalling devices) operation option setting
0 – sign. dev. operation acc. to 0 option
1 – sign. dev. operation acc. to 1 option
EXT.AL.OPTION - 0
The description of the signalling devices operation in option 0 and 1 is contained in p. 5.10.
0001 z2 17 : 15 : 48
Содержание Ignis 1000
Страница 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Страница 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Страница 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Страница 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Страница 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Страница 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...