20
ID-E299-001GB
Note:
The delay value set is common for all zones.
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, set the proper zone number and ‘1’ (on the last
display position) that results in the chosen zone delay enablement.
Two-stage alarm with zone-time interdependence
Programming:
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, set the number of one of the interdependent zones
and variant number equal to ‘2’,
- using the FUNCTION push button, select the function,
- with the SELECTION and SET push buttons, set the proper delay time in minutes (0..9) – the X
position in the display and in seconds (00…59) – two following positions XX.
Note:
The delay value set is common for all zones.
- using the FUNCTION push button, select the function,
- with the SELECTION and SET push buttons, set the number of the first interdependent zone
and enter ‘1’ (on the last display position) that results in the chosen zone delay enablement,
- repeat the above operation for the second zone of the interdependent zones pair so that each
zone (of the pair) has the delay enabled.
Note:
Entering the variant #2 for any zone results in an automatic creation of a dependent zone pair and
automatically assigns the variant #2 to the second zone constituting the pair. Similarly, a failure to
choose the variant #2 and assigning the variant #0 or #1 to a zone constituting the pair results in an
automatic loading of the variant #0 for the other zone of the pair.
It is possible to create interdependent zone pairs using only zones of neighbouring numbers as
shown below:
-
1
st
pair – zones #1 and #2
-
2
nd
pair – zones #3 and #4
-
3
rd
pair – zones #5 and #6
-
4
th
pair – zones #7 and #8
-
………………………………………..
-
12th pair – zones #23 and #24.
DELAYS ON z. 01 - 1
VARIANT z. 01 - 2
DELAY X’ XX’’
DELAYS ON z. 01 - 1
Содержание Ignis 1000
Страница 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Страница 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Страница 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Страница 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Страница 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Страница 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...