5.3.2 General alarm relays actuation delay programming
1’30 – delay time (example)
1’ – minutes (1…9)
30 – seconds (0…59)
DELAY - 1’ 30
The delay time setting change is possible with the following push buttons:
SET^ - increase
SET` - decrease.
5.3.3 General alarm signal transmission delay disablement/re-enablement
zone number 1…16 or 24
1 – delays enabled
0 – delays disabled
DELAYS ON z. 01 - 1
The setting change - with the SET^ and SET` push bu[ons.
The function requires, apart from selecting the zone number (1…16 or 24), entering ‘1’ – if the delay
is to be enabled or entering ‘0’ – if the delay is to be disabled. It allows for delay disablement of
chosen detection lines, any alarm from which should actuate the general alarm relays immediately
(e.g. a detection line with ROP manual call points installed). Any detecting line acknowledged alarm
with a delay enabled (which value is set using the DELAY function) causes properly delayed general
alarm relay activation. Lack of alarm acknowledgment shortens the delay time to 30 s. In the
‘personnel absent’ mode the control panel reduces the delay time to zero. The described delay
concerns only the general alarm relays; zone relays operate always without any delay.
The general fire relay activation transmission delay programming is linked with alarm variant
programming (see p. 5.3.6).
5.3.4 Event memory reset
0 – reset function disabled
1 – reset function enabled
MEMORY RESET - 0
Note:
The event memory reset performance is possible after the reset function initiation with the SET^
push button and pressing the (P13) RESET push button.
Содержание Ignis 1000
Страница 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Страница 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Страница 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Страница 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Страница 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Страница 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...