zone number 1…16 or 24
0 – testing enabled
1 – testing disabled
TESTING ON z. 01 - 0
5.2.3 Zone disablement/re-enablement
A disablement/re-enablement of a zone (detection line) is possible using the following function:
zone number 1…16 or 24
0 – zone enabled
1 – zone disabled
ZONE ON z. 01 - 0
5.2.4 Faults readout
In order to read the faults out, it is necessary to select with the FUNCTION push button the following
indication on the display:
Afterwards, using the SET^ push bu[on recall the messages informing on the current faults
registered in the system.
The below table lists the possible faults with their clarifications.
BZ3 FUSE FAULT
BZ3 fuse fault
BATT.VOLTAGE DECR.
Battery voltage drop
MAINS POW.SUP.FAULT
230 V mains power supply fault
BATTERY FAULT
Battery cluster or its circuit fault
EARTH FAULT
Damage of insulation between control panel and
grounding
LACK OF CHARGING
Charging circuit fault of interruption
SYSTEM FAULT
Control panel controller program execution
disruption
FAULT READOUT