*Note: Link Manager converts the temperature to degrees F as the default
temperature units.
Use the “CVRC” command to obtain the number of Enumerated Engineering Units
entries in the table. (This includes all the predefined enumerations.)
Use the “CVR” command with the row number (starting at 1) to read an entry in the
table.
Use the “CVS” command to set or override an entry (including predefined entries)
using the enumerated number.
Use the “CVC” command to clear the table. The Link Manager will repopulate the
table with the predefined Enumerated Engineering Unts entries.
Examples
Command: CVC
Response: CVC
Remarks: clear the Enumerated Engineering Units table.
Command:
CVRC
Response: CVRC,4
Remarks : read the number of entries in the Enumerated Engineering
Units table
Command:
CVR1
Response: CVR1,0,0.00305,0.00000,%,1
Command:
CVR2
Response: CVR2,61,0.02440,0.00000,%RH,1
Command:
CVR3
Response: CVR3,62,0.05495,-40.00000,degF,1
Command:
CVR4
Response: CVR4,63,0.05495,-40.00000,degF,1
Remarks: read 4 entries from the Enumerated Engineering Units table
Command:
CUR
Response: CUR,30,3,30,na,00000000
Remarks: Pass-Thru Media Callout table is empty
Command:
CVS2,0.0244,0,psi,1
Response: CVS2
Remarks:
Add a new entry for Enumerated Engineering Units value #2.
At 100 PSI the raw sensor reading is 4095.