![Point Six Link Manager 4010-43 Скачать руководство пользователя страница 119](http://html1.mh-extra.com/html/point-six/link-manager-4010-43/link-manager-4010-43_manual_1570778119.webp)
Link Manager Manual
Appendix
117
Appendix
Models
Model
Media
Description
4010-43
Ethernet Port
1 Serial Port
Built in 900 Mhz
transceiver
Built in 418 Mhz
receiver
1 RS485 Port
Link Manager is ready to receive
transmissions from 900 Mhz
sensors, 900 Mhz Point
Repeaters., 418 Mhz sensors and
wired RS485 sensors. (Shown on
cover page of manual.)
Transmissions can be sent through
the 900 Mhz transceiver or RS485
port to output sensors.
Troubleshooting
Sensor Issues
Cannot Register Sensor via AutoAdd
1.
Make sure the Point Sensor has been configured using the Point Sensor Utility
(make sure the Point Sensor Utility has been configured properly). Reconfigure
the Point Sensor using the Point Sensor Utility.
2.
Make sure the Point Sensor and the Link Manager are using the same Hop Table
setting. The default is 3.
3.
Make sure the AutoAdd mode is enabled. The Link Manager will display the
line “AutoAdd:
xxxx
seconds” if AutoAdd mode is enabled. If AutoAdd mode
is disabled, no sensors will be added via radio.
4.
Make the sensor is turned on.
5.
The sensor can only be added if the service button is pressed or magnet swiped.