Link Manager Manual
Commands
67
Sensor I/O Definitions
Sensor
Type
Type
Description
No.
I/O
Pts
I/O
Point
Types
Example I/O Point Setup String
1
Temperature
(Point Temp)
1
Analog
(A0.1125,32.0000,degF,1,0)
2
Humidity/
Temperature
(Point Humid)
2
Analog,
Analog
(A1,0,%RH,0,0)
(A0.1125,32.0,degF,1,0)
3
Light (Point
Light)
1
Analog
(A0.02440,0.00000,%,2,0)
4
IButton (Point
PIR)
1
Data
(DF)
5
Analog (Point
Analog)
1
Analog
(A0.02440,0.00000,%,2,0)
6
IR Counter,
and LSX
3
State,
Integer,
Integer
(SBlocked,Open,Closed,Error)
(I1,0,open,0)
(I1,0,close,0)
8
Analog with
Data
2
Analog,
Data
(A0.02440,0.00000,%,2)
(DT)
9
Analog /
Temperature
2
Analog,
Analog
(A0.244,0.0,PSI,1,0)
(A0.1125,32.0000,degF,1,0)
11
Discrete
1
State
(Soff,on)
12
Thermistor
1
Analog
(A0.1125,32.0000,degF,1,0)
13
16-bit signed
Analog
1
Analog
(A0.02440,0.00000,%,2,0)
14
Counter
Temperature
3
State,
Integer,
Analog
(STrans.,Open,Closed,Error)
(I1,0,count,0)
(A0.1125,32.0000,F,1,0,0)
15
Fast Counter
Temperature
4
Integer,
Analog,
Integer
Analog
(I1,0,count,0)
(A0.1125,32.0000,F,1,0,0)
(I1,0,sec,0)
(A0.1000,0.0000,Rate,1,0,0)
16
Alarm
Temperature
4
State,
State,
Analog,
Data
SOK,Alarm,0)
(SOK,Alarm,0)
(A0.1125,32.0000,F,1,0,0,0)
(DT,0)
17
Space
Temperature
Override
3
Analog,
State,
Data
(A0.1125,32.0000,F,1,0,0,0)
(SNormal,Occupy,Unocc.,0)
(DT,0)
18
Directional
Counter
3
State,
Integer,
Integer
(SBlocked,Okay,PwrAlrm,BattAlrm,0)
(I1,0,count,0,0)
(I1,0,count,0,0)
20
ID Reader
4
State,
State,
State,
Data
(SBatt OK,LowBatt,0)
(STamp OK,Tamper,0)
(SClosed,DoorOpen,HeldOpen,HeldOpen,0)
(DT,0)
23
Proximity2
5
State,
Integer,
Integer,
Integer,
State
(Sstate1,Object,NoObject,state2,0)
(I1,0,count,0,0)
(I1,0,sec,0,0)
(I1,0,sec,0,0)
(S1,2,3,4,0)
27
Dual Analog
1
Analog
(A0.00305,0.00000,%,2,0,0)
28
Dual Analog
2
Analog
(A0.00305,0.00000,%,2,0,0)
Содержание Link Manager 4010-43