108
Commands
Link Manager Manual
‘S’ - Get Status Data Command
Command Options
S
Command/Response Syntax
Command:
S
Response:
S,
sensor count
,
last setup change time, alarm time
,
periodic time,
job count, output count, timer count, match count, scheduled output count
Parameters
Where:
sensor count
– number of sensors in the sensor list
last setup change time
– time and date of the last setup change
(
mmddyyhhnnss)
alarm time
–
na
– Not used by the Link Manager.
periodic timer
– na – Not used by the Link Manager.
job count
– number of jobs in the job list. Not used by the Link Manager.
output count
– number of outputs in the output table. Not used by the Link
Manager.
timer count
– number of timer outputs in the timer table. Not used by the
Link Manager.
match count
– number of matches in the match table. Not used by the Link
Manager.
scheduled output count
– number of schedule outputs. Not used by the Link
Manager.
failed
– resetting the periodic alarm time failed: “,F”; blank if succeeded.
Not used by the Link Manager.
Login Level
Login Level:
Data
Description
Returns the number of sensors in the configuration table.
The
last setup change time
can be used by host to determine if the setup has been
changed by a second host.
Examples
Command:
S
Response: S,6,082503153753,na,na,0,22,0,6,2
Remarks: 6 sensors are set up; last setup change occurred at 08/25/03
15:37:53.