Commissioning
Operating Manual PSEN op2B/1 Series
1003357-EN-02
43
If any of these requirements are not met, the safety light grid switches immediately to a safe
condition when supply voltage is switched on.
7.1.3
Set muting timeout
Time monitoring for the muting function can be set to
}
10 minutes or
}
to ∞
gestellt werden.
When the unit is delivered, this is already preset to 10 minutes.
CAUTION!
If time monitoring for the muting function is set to ∞, the muting function is
not cancelled until the muting sensors are no longer active.
This setting does not comply with the specifications of EN ISO 61496-1.
Avoid a situation in which sustained muting is not detected.
Procedure for setting to ∞
Set DIP switches 1 and 5 to OFF.
7.1.4
Activate EDM
EDM only needs to be activated if the contactors are controlled directly.
Procedure for activating EDM
1. Connect the inputs of the external control elements.
Connect the inputs to a N/C contact with 24 VDC on the device to be monitored.
2. Activate EDM on the DIP switch.
Set DIP switches 3 and 7 to OFF.
1
2
3
4
5
6
7
8
ON
Fig.: DIP switch 3 and 7 in OFF position = EDM activated
7.1.5
Restart after unit is triggered
Select how the restart is controlled after the OSSDs have been switched off.
}
Without restart interlock
Status when delivered
}
With restart interlock
Set DIP switches 4 and 8 to OFF.