Project configuration
Operating Manual PSEN op2B/1 Series
1003357-EN-02
33
Icon
Unit
Minimum
value
Maximum value
Description
L
cm
D
MutingOff
Length of the object that trig-
gers the muting status as it
passes the muting sensors
V
cm/s
4.125
250
Speed at which the object is
moving
D
A-B
cm
< D
MutingOff
Distance D
A-B
must be
covered in max. 4 s
Distance between the sensors
connected to the same muting
input A1 and B1, and between
A2 and B2
D
MutingOff
cm
L
Distance between muting
sensor A1 and the position
from which the muting function
is turned off again, when con-
sidering the transport direction
from A1 to A2
Distances for muting with 4 sensors
Muting in one direction
A1
B1
[1]
D
A-B
D
MutingOff
L
V
Fig.: Distances between muting sensors - 2 muting sensors
Legende
[1] Safety light grid
A1 First muting sensor
B1 Second muting sensor
Icon
Unit
Minimum
value
Maximum value
Description
L
cm
D
MutingOff
Length of the object that trig-
gers the muting status as it
passes the muting sensors
V
cm/s
4.125
250
Speed at which the object is
moving
D
A-B
cm
< D
MutingOff
Distance must be
covered within 4 s
Distance between the mut-
ing sensors A1 and B1