![Pilz PSEN op2B-2-050/1 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/pilz/psen-op2b-2-050-1/psen-op2b-2-050-1_operating-manual_1556675040.webp)
Installation and wiring
Operating Manual PSEN op2B/1 Series
1003357-EN-02
40
6.4.5
Earthing the safety light grid
Attach the earth connection in the drill hole provided on the connector side of the safety
light curtain using the screw provided (see diagram).
Identify the earthing contact using the adhesive label provided.
[1]
Legend
:
[1]: Drill holes for earthing screw. The drill holes are on the bottom of the safety light grid, at
the same height on the right
and left.
6.4.6
Connections for muting
Wire the muting sensors using the connection cable provided (see
Order reference for ac-
cessories, section on muting accessories [
60]
).
}
For L-muting:
PSEN op cable M12 4-p. 0.75m L-muting
}
For T-muting and for cross muting:
PSEN op cableset
The connection cable is used to
}
Connect the muting sensors to the safety light grid
}
Supply voltage to the muting sensors via the safety light grid.