Function description
Operating Manual PSEN op2B/1 Series
1003357-EN-02
21
}
Muting cannot be activated when the safety light grid
is in a safe condition (red LED is
lit, protected field is interrupted).
t
t
Moff
Muting
function
On
Off
Input
Muting 1
Input
Muting 2
On
Off
On
Off
t
AB
Fig.: Timing diagram for L-type muting
Legend
t
AB
: Time from the activation of the first sensor to the activation of the second sensor,
max. 4 s
t
Moff
: Once this time has elapsed, the muting function switches off automatically, max. 8 s
t
Muting
function
On
Off
Input
Muting 1
Input
Muting 2
On
Off
On
Off
t
AB
Fig.: Timing diagram for T-type muting
Legend
t
AB
: Time from the activation of the first sensor to the activation of the second sensor,
max. 4 s