Operation
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 84
The system checks whether the conditions are met. When the conditions are met,
restoring of the configuration is started.
2. Depending on the type of difference between memory module and PSEN sc M the
restoring of the configuration varies.
Serial numbers differ: On the display of the master unit, CFG NO MATCHING is shown.
Continue by selecting the data for the restore.
Topology or MIB files vary: On the display of the master unit WAITING CONF is shown.
Continue the configuration in PSENscan Configurator.
3. Use the buttons on the display of the master unit to select the data to be used for re-
store.
Display master unit:
Restore cfg
: The configurations in the memory module are used. Confirm the selection
with
Confirm
and the configuration is copied from the memory module into PSEN sc M.
Continue checking the configuration.
cfg from GUI
: The configuration created newly in the PSENscan Configurator is used.
Confirm your selection with
Confirm
and continue with Create new configuration in
PSENscan Configurator.
4. Display master unit:
Confirm
/
Cancel
Display slave unit: CHECK MASTER
Confirm your entry with
Confirm
5. Checking the configuration
Display master unit: RESTORE FAILED. Could not copy the configuration successfully.
Continue by selecting the data for the restore.
Display master unit: RUN TEST MODE
On the display of the master unit, select
Enter Test
. Test operation starts. Continue
with accept or reject configuration.
6. Accept or reject configuration
Test operation is complete.
Select
Validate conf
to accept the configuration. The safety laser scanner is ready for
operation again.
Select
Reject conf
to reject the configuration. Continue by selecting the data for the re-
store.
7. Create new configuration in PSENscan Configurator
Display master unit: WAITING CONF
Display slave unit: CHECK MASTER
Configure the safety laser scanner in PSENscan Configurator.