Wiring
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 53
[1]
Legend
[1] Protective membrane
5. Remove the label [1] from the memory module and insert the memory module at the
safety laser scanner.
6. Fix the screw of the memory module with a torque of 1 Nm.
7. Place the protective cover at the safety laser scanner and screw the protective covers
with 1 Nm.
6.5
Connection to PSENscan Configurator
The configuration of the safety laser scanner PSEN sc M 3/5 series is carried out in
PSENscan Configurator on a configuration PC.
Please note:
}
Ensure that the software PSENscan Configurator is installed on the configuration PC.
}
Ensure that the safety laser scanner is switched off when creating a connection to the
configuration PC.
100BaseTX cable
Bit rate
100 MBit/s
Max. segment length
100 m
Medium
STP
(shielded twisted pair)
*1
2 pairs
Category 5
*2
Connection
4-pin M12 male connector /4-pin RJ45 male
connector
Topology
Point-to-point/hub
(hub, switch)