First commissioning
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 73
Device
You can enter a title for the connected device under
Name
.
Safety laser scanner arrangement
You can enter a title for the safety laser scanner arrangement under
Name
.
You can enter names for the devices in the safety laser scanner arrangement under
Device.
Click on the arrow
. The next window is opened:
Output configuration
. The number
of OSSD pairs is already selected.
4. Select
Warning zone
= 0.
If
Warning zone
= 0, the warning zone is activated. The output Pin 1 is automatically
set to NOFUNCTION. The output cannot be used.
Outputs Pin 5 and 6 are reserved for OSSD 1 and OSSD 2 and cannot be changed.
Click on the arrow
. The next window
Configure zone sets
is opened.
5. Select
Zone set
= 3 and enter for the PINs 1, 3 and 4 each the
Zone switching
. Enter
the input delay.
For the configuration of switchable zones the PINs 1, 3 and 4 have to be assigned to
the zone sets. You can make the assignment automatically using PSENscan Configur-
ator or perform it manually.
Automatic assignment using PSENscan Configurator
Click
for automatic specification of the coding of zone sets
Manual assignment
For
Zone set 1
enter
AS3 = 1
.
For
Zone set 2
enter
AS2 = 1
.
For
Zone set 3
enter
AS1 = 1
.
Assignment of input signals
For PIN 1, enter AREA SWITCH 3.
For PIN 3, enter AREA SWITCH 1.
For PIN 4, enter AREA SWITCH 2.
Click on the arrow
. The next window
Input configuration
is opened.