Project configuration
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 46
5.13.4
Dynamic muting
When
Activate muting
is selected for one of the inputs 3, 9, 10 or 11, muting can be activ-
ated and deactivated dynamically.
}
Conditions for the occurrence of muting
– One of the inputs 3, 9, 10 or 11 is connected to a controller and it receives a high sig-
nal from there when muting is to be activated
– When configuring the inputs,
Activate muting
is configured for this in PSENscan
Configurator
– The first sensor has detected a conveyed material and the second sensor also detec-
ted it max. 4 s later
or
the first sensor and the second sensor detected conveyed ma-
terial simultaneously
5.14
Override
The override function can be used for the three types according to the timing diagrams.
}
Single-channel pulses
}
Activation by rising edge
}
Activation by rising signal (only when using the 12-pin connection)
Protective zone
Status
Override
Single-channel
Pulse
On
Off
On
Off
24 V
0 V
t
2 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
Fig.: Timing diagram for override function single-channel pulses