First commissioning
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 74
6. For
Restart
select the value
Automatic
and define the
Recovery time
(min. 200 ms,
max. 60000 ms).
Select whether
EDM
is to be activated. When EDM is activated, a PIN must be as-
signed to the EDM input.
7. Click on the arrow
. The next window
Configure detection capability
is opened.
8. Under
Multiple evaluation
, define the number of consecutive scans needed for detec-
tion.
Increasing the number of consecutive scans will increase the response time of the
safety laser scanner.
9. Select the
detection capability [mm]
for this safety laser scanner. Define the value for
Safety zone
or for
Warning zone
.
10. Select
Dust filter level
(level 1 = low, level 3 = high).
A higher level of dust filtering requires a longer safety distance.
WARNING!
Loss of safety function due to a safety distance that is too low
Depending on the application, serious injury or death may result.
}
Depending on the degree of dust filtering, it is necessary to consider an
allowance for calculating the safety distance when installing the safety
laser scanner near intense light sources or reflective surfaces into ac-
count (see
Distance to intense light sources and to reflective
– When calculating the safety distance, ensure that the allowance is
considered depending on the dust filtering.
– Ensure that the new safety distance fulfils the specifications of the
safety assessment.
11. Click on the arrow
. The next window
Configure zones
is opened.
Create the zones using the symbols in the tool bar on the right-hand side.