Function description
Operating Manual PSEN sc M 3/5 series
1005055-EN-02
| 22
The muting sensors are connected to muting inputs 1 and 2. The muting sensors must be
positioned and installed at a right angle to the safety laser scanner (see
wiring [
).
}
When the muting state of the safety laser scanner is detected, the safety laser scanner
triggers the configured actions for the muting state (e.g. switch on warning lamp or warn-
ing sound).
}
Muting can be used in various versions.
– L muting: Transport of material in one direction
– T muting: Transport of material in two directions
– Dynamic muting: Available for L muting and T muting
In addition to the conditions for L muting and T muting, activation and deactivation of
the muting state can be controlled by the connected safety controller.
[1]
[2]
[3]
[4]
Legend
[1] Protective zone
[2] Muting zone
[3] Transported material
[4] Safety laser scanner
CAUTION!
Risk of injury due to loss of the safety function
In a muting state, the OSSDs continue to be switched on. The connected
machine remains in operation and represents a potential hazard.
– Prevent access to the danger zone during muting.
}
The muting state is shown by the muting lamp and in the display of PSEN sc M 3/5
series.