8.5 Register setting
The functional code is 10H.
The main station can set one or more than one register values, and the register operations not
defined are invalid.
Write register format
(
Main station
→
PMAC735
)
Response format
(
PMAC735
→
main station
)
Slave station address
1 byte
Slave station address
1 byte
Functional code 10H
1 byte
Functional code 10H
1 byte
Start address
2 bytes
Start address
2 bytes
Number of registers
2 bytes
Number of registers
2 bytes
Byte number (2
×
number of registers)
1 byte
CRC check code
2 bytes
Data of the first register
Data of the second
register
……….
CRC check code
2 bytes
Содержание PMAC735
Страница 7: ...7 1 1 Pictures of the main unit Side view Rear view 1 2 Picture of the extension module Rear view...
Страница 18: ...18 B Low voltage 3 phase 3 wire delta connection 3 CTs C Low voltage 3 phase 3 wire delta connection 2 CTs...
Страница 19: ...19 D High voltage 3 phase 4 wire star connection E High voltage 3 phase 3 wire delta connection 3 CTs...
Страница 32: ...32 4 2 7 Frequency Press the key once and you will see the frequency data S1 S2 S3 S4 RL1 RL2 RL3 RL4...