MAINTENANCE
4-26
/ Husky 12 Foam System
© 2017 Pierce Manufacturing Inc. All Rights Reserved.
Question
Reason for Question
Test Procedure
G. Is the ground circuit OK?
The foam system must
have an adequate ground
(continuity) for the system
to operate.
Check ground circuit (ckt# 1640K). Refer to
for additional
circuit information.
1149
Question
Reason for Question
Test Procedure
H. Is the flowmeter operating
correctly?
The flowmeter provides
the foam system with
information on how much
water is being flowed. No
signal from the flowmeter
will result in the foam
system not operating.
If “GPM” appears on the display, the flowmeter
is OK. If “GPM” does not appear, replace the
flowmeter.
Repair ground circuit.
No
Yes
Replace flowmeter, see
service group 7950-P-001.
No
Yes