6.6.5 X10 Enable-Connector
The power stage can be deactivated independent of the logic signals (X10 enable
connector).
The opto-decoupled Enable inputs A and B are used to activate the motor supply.
Both
Enable inputs must be wired for activation!
The Monitor Enable output is used to check the Enable inputs A and B, i.e. when both
inputs are wired, the Monitor Enable output is set to ‚high’.
The function Enable doesn´t fulfill
‘Protection against unexpected start‘
according to EN 945-1 for application
in the extended safety sections.
Fig. 36: X10 Connector Enable
The Enable inputs A and B can be permanently activated by bypassing the inputs with
the+24 V
DC
output. This will work only, if +24 V
DC
is supplied to the X4 connector.
Fig. 37: Activation of A and B inputs
A deactivation of the Enable signals during increasing stop and run current
values can cause an error and the axes will be stopped by an emergency stop. If
the Enable functionality should be checked e. g. after power-on, we recommend
either to reduce the current parameters or to detect the extern deactivation in the
Minilog program by commands and to reset the axes (see manual MiniLog).
Minilog command for reading the system status:
ST
, Bit 5 is set (32
Dec
) = input Enable is OK
See also MiniLog for MCC programming manual.
.
Содержание MCC-1
Страница 13: ...Manual MCC 1 MA 1249 A009 EN 12 1 6 Declaration of Incorporation...
Страница 26: ...phytron 25 MA 1249 A009 EN 1 Fig 12 Wall mounting MCC 1 dimensions Fig 13 Rail mounting MCC 1 dimensions...
Страница 45: ...Manual MCC 1 MA 1249 A009 EN 44 Fig 38 Enable Connector wiring...
Страница 54: ...Phytron GmbH Industriestra e 12 82194 Gr benzell T 49 8142 503 0 F 49 8142 503 190 www phytron eu...