Manual MCC-1
MA 1249-A009 EN
18
4 Design Requirements
4.1 Electromagnetic Compatibility (EMC)
4.1.1 Remarks
WARNING
Risk of injury by interference of signals and devices!
Perturbed signals can cause equipment to react unexpectedly.
• Connect the controller to
the EMC requirements
.
•
In electrically noisy environments ensure the correct execution of the EMC
measures. Disregarding these precautions can cause death, serious injuries
or material damages.
4.1.2 EMC Measures
EMC Measures
Effect
Device
Mounting
Use cable clamps for shielding, connect
metallic parts at a large area.
Good conductivity due
to planar contacts.
Connect the housing via cable diameter
more than 2 mm
2
with potential equalisation.
Reduction of mutual
interference.
Fit switching devices such as contactors,
relays or solenoids with interference or
spark suppressors (e. g. diodes, varistors,
RC elements).
Cabling
Keep cables as short as possible.
No
“safety loops“.
Avoidance of capacitive
and inductive
interference
Connect the shielding of all shielded cables
to the housing by the cable clamps to a
large area.
Reduction of EMC
emissions.
Lay the cables spatially separated from
each other (distance at least 20 cm):
signal and power cables
power and master cables
line filter input and output cable
Avoidance of mutual
interference
Содержание MCC-1
Страница 13: ...Manual MCC 1 MA 1249 A009 EN 12 1 6 Declaration of Incorporation...
Страница 26: ...phytron 25 MA 1249 A009 EN 1 Fig 12 Wall mounting MCC 1 dimensions Fig 13 Rail mounting MCC 1 dimensions...
Страница 45: ...Manual MCC 1 MA 1249 A009 EN 44 Fig 38 Enable Connector wiring...
Страница 54: ...Phytron GmbH Industriestra e 12 82194 Gr benzell T 49 8142 503 0 F 49 8142 503 190 www phytron eu...