6.5 X5 Com Communication Interface
The X5 Com communication interface is available as USB, RS 232(4-wire), RS 485 or
Ethernet connection.
Factory setting:
57 600 Baud
8 Data bits
1 Stop bit
No parity
Protocol::
<STX>
|
Address | Data | Separator | Checksum
| <ETX>
Baud rate
and
Interface parameters
can be modified after installation of MiniLog-Comm
in the menu item
Options/Interface Parameters.
IMPORTANT
If the MCC-1 is connected via Ethernet ensure that the
IP address is
created by DHCP
(dynamic IP configuration).
Differently generated IP addresses are not identified.
i
When the MCC-1 is connected to the PC by USB-interface, USB drivers have
to be installed on the PC.
i
The MCC-1 is connected to the PC as a stand-alone device.
An USB converter is needed, if several controller should be connected by
USB. It is mounted either external or at the first MCC-1 with RS 485
interface.
See chapter 6.5.3 RS 485 interface.