FL SWITCH IRT
PHOENIX CONTACT
8289_en_04
–
Value = 4 - Port is administratively disabled
6.2.3
Configuration via the engineering tool
The universal parameter editor (UPE) can be used to configure the switch via the engineer-
ing tool (PC Worx).
–
Activation/deactivation of PROFINET alarms
–
Configuration of port mode
–
Configuration of port state
6.2.4
PROFINET flashing function
If the switch is requested to flash in PROFINET mode by the engineering tool, the port LEDs
flash.
6.2.5
Device naming
To start up the switch in “PROFINET” operating mode, each device must be assigned a
unique name once.
•
Complete a device search via the engineering tool (“Read in PROFINET” function
PC Worx) during which all the accessible devices in the network are listed.
•
After identifying unknown devices via the specified MAC address or the “flashing” func-
tion, the device name configured in the engineering tool is saved permanently on the
switch using the “Assign Name” function.
6.2.6
Operating in the PROFINET environment
A switch that has already been assigned a name starts without an IP address and waits for
the assignment of an IP configuration (flashing of the LED for the currently active mode).
Once the project has been transferred and downloaded to the controller, the controller im-
plements startup and configuration. As soon as a communication relationship has been suc-
cessfully established between the switch and the controller, the switch starts its manage-
ment interfaces. The switch indicates that the PROFINET connection has been established
correctly by means of an entry in the event table.
6.3
PROFINET alarms
The IRT can send the following alarms:
–
Redundant power supply missing (management agent alarm)
All the alarms are deactivated when the device is started.
The device name can also be assigned via WBM.
Содержание 2700689
Страница 1: ...User manual IRT switch for PROFINET realtime...
Страница 12: ...FL SWITCH IRT 12 52 PHOENIX CONTACT 8289_en_04...
Страница 22: ...FL SWITCH IRT 22 52 PHOENIX CONTACT 8289_en_04...
Страница 34: ...FL SWITCH IRT 34 52 PHOENIX CONTACT 8289_en_04...
Страница 50: ...FL SWITCH IRT 50 52 PHOENIX CONTACT 8289_en_04...