FL SWITCH IRT
PHOENIX CONTACT
8289_en_04
Figure 3-6
Basic circuit diagram for the signal contact
3.3.3
Assignment of the RJ45 Ethernet connectors
In the event of non-redundant voltage supply, the switch indicates the failure of a supply
voltage by opening the signal contact. You can prevent this error message by connecting
the supply voltage to both terminals in parallel, as illustrated in
, or by carrying
out the corresponding configuration in web-based management.
Table 3-1
Pin assignment of RJ45 connectors
Pin number
10Base-T/10 Mbps
100Base-T/100 Mbps
1
TD+ (transmit)
TD+ (transmit)
2
TD- (transmit)
TD- (transmit)
3
RD+ (receive)
RD+ (receive)
4
-
-
5
-
-
6
RD- (receive)
RD- (receive)
7
-
-
8
-
-
R 1
R 2
6 7 8 4 0 0 1 5