Mounting and installation
8289_en_04
PHOENIX CONTACT
17 / 52
3.4
Installing the IP67 switch
3.4.1
Connecting the 24 V DC supply voltage
The switch is operated using a 24 V DC voltage (US1 - bus logic), which is applied via COM-
BICON/AIDA. The voltage supplies the switch on its own. The voltage US2 (sensor voltage)
will only pass through the switch (see figure below). Should you wish to supply the device
redundantly, two appropriate power supplies must be connected in parallel to US1. Ensure
that the power supplies used are suitable for parallel operation.
Figure 3-7
Principle of internal voltage routing
3.4.2
Signal contact
The switch has a floating signal contact. An error is indicated when the contact is opened.
A B-coded M12 connector (located on the device) is used to connect the signal contact.
Pin 1 and Pin 4 are used for the signal contact. Pins 2, 3 and 5 are not used.
Figure 3-8
Pin assignment of the signal contact
FL SWITCH IRT IP TX/3POF
Ord. No. 27 00 697
MAC - Address
X1
X2
X3
X4
US1
US2
FAIL
BF
FO
LNK
ACT
X5
US1 GND US2 GND PE
X5
US1 GND US2 GND PE
X6
US1 GND US2 GND PE
X6
US1 GND US2 GND PE
X7
R1 R2
X7
R1 R2
X8
MEM
X8
MEM
00.A0.45.1B.D2.1D
Sno.: 200221439
US1 GND US2 GND
FE
US1 GND US2 GND
FE
Device supply
Internal
jumpers
1
2
3
4
5
Содержание 2700689
Страница 1: ...User manual IRT switch for PROFINET realtime...
Страница 12: ...FL SWITCH IRT 12 52 PHOENIX CONTACT 8289_en_04...
Страница 22: ...FL SWITCH IRT 22 52 PHOENIX CONTACT 8289_en_04...
Страница 34: ...FL SWITCH IRT 34 52 PHOENIX CONTACT 8289_en_04...
Страница 50: ...FL SWITCH IRT 50 52 PHOENIX CONTACT 8289_en_04...