Startup and functions
8289_en_04
PHOENIX CONTACT
19 / 52
4
Startup and functions
4.1
Basic settings
4.1.1
Delivery state/factory settings
Upon delivery or after the system is reset to the default settings, the following functions and
properties are available by default:
–
The user name is “admin”
The password is “private”.
–
All IP parameters are deleted. The switch has
no
valid IP parameters:
IP address:
0.0.0.0
Subnet mask:
0.0.0.0
Gateway:
0.0.0.0
–
PROFINET DCP is activated as the addressing mechanism.
–
All available RJ45 ports are activated with the following parameters:
- Auto negotiation
- Autocrossing
–
All counters of the SNMP agent are deleted.
–
Web server and SNMP agent are active.
–
MRP is disabled.
–
In the case of the IP20 switch, the alarm contact only opens in the event of non-redun-
dant power supply.
–
The aging time is set to 40 seconds.
–
The switch is in “PROFINET” operating mode.
The basic Ethernet functions do not have to be configured and are available when the
supply voltage is switched on.