Operation as a PROFINET device
8289_en_04
PHOENIX CONTACT
37 / 52
–
Automatic - you can enter the devices via the “Import PROFINET” function.
This
means that you can access them in the network via DCP (Discovery and Con-
figuration Protocol). In the meantime, ensure that the devices are supplied with
power and are operated in “PROFINET” operating mode.
6.2.2
Configuring the switch as a PROFINET IO device
Once all switches have been added to the bus configuration, the following settings must be
made for the individual switches via the “Detail View” tab (device details):
–
The PROFINET device name must be checked and modified if necessary.
–
The IP address and the subnet mask must be checked and modified, if necessary.
–
The update time for inputs should be set to “
512 ms
” (default).
–
The update time for outputs should be set to “
512 ms
” (default).
–
The interface modules must be selected from the module catalog and added to the sta-
tion.
Figure 6-2
Device details with modified settings
The PROFINET variables can then be created and used in the control program.
In addition to the “PNIO_DATA_STATE” standard variable, the switch provides the link sta-
tus as a process data byte for each port. If the “PNIO_DATA_VALID” bit for the “PNIO_-
DATA_STATE” variable declares the switch process data as valid, the process data item for
a port can have the following values (see
Section “Additional process data” on page 39
–
Value = 0 - No active link
–
Value = 1 - Active link
–
Value = 3 - Link present, but peer cannot establish link (only for FX ports - Far End Fault
Detection)
Содержание 2700689
Страница 1: ...User manual IRT switch for PROFINET realtime...
Страница 12: ...FL SWITCH IRT 12 52 PHOENIX CONTACT 8289_en_04...
Страница 22: ...FL SWITCH IRT 22 52 PHOENIX CONTACT 8289_en_04...
Страница 34: ...FL SWITCH IRT 34 52 PHOENIX CONTACT 8289_en_04...
Страница 50: ...FL SWITCH IRT 50 52 PHOENIX CONTACT 8289_en_04...