VersiStart p III
64
Parameter Group
Default Setting
20
Advanced
20A
Tracking Gain
50%
20B
Pedestal Detect
80%
20C
Bypass Contactor Delay
150 ms
20D
Model Rating
0020
20E
Screen Timeout
1 minute
10.5 1 Motor Details
1A –
Command Source
Options:
Digital Input
(default)
The VersiStart p III will accept start and stop
commands from the digital inputs.
Network
The VersiStart p III will accept start and stop
commands from the communication expansion
card.
Remote Keypad
The VersiStart p III will accept start and stop
commands from the Remote Keypad.
Clock
The VersiStart p III will start and stop as
scheduled in parameters 4A to 4V.
Smart Card
The VersiStart p III will accept start and stop
commands from the smart card.
Smart Card + Clock The VersiStart p III will accept start commands
from the smart card if they are within the
operating schedule set in parameters 4A to 4V.
A stop command from the smart card will be
accepted regardless of the schedule.
Description:
Selects the command source for controlling the soft starter.
1B – Motor Full Load Current
Range:
Model dependent
Description:
Matches the starter to the connected motor's full load current. Set to
the full load current (FLC) rating shown on the motor nameplate.
1C – Locked Rotor Time
Range:
0:01 - 2:00 (minutes:seconds)
Default:
10 seconds
Description:
Sets the maximum length of time the motor can sustain locked rotor
current from cold before reaching its maximum temperature. Set
according to the motor datasheet.
1D – Locked Rotor Current
Range:
400% - 1200% FLC
Default:
600%
Description:
Sets the locked rotor current of the connected motor, as a percentage
of full load current. Set according to the motor datasheet.
Содержание VersiStart p III 105