29
VersiStart p III
5.5 Control Voltage
Control Voltage Terminals
A3 A1 A2
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
B4 B5 10 11 12 13 14 15 21 22
33 34 41 42 44 53 54
A3 A1 A2
Connect the control supply according to the supply voltage being used.
•
VS p III xxx xxxxB-
C1
(110~120 VAC): A1, A2
•
VS p III xxx xxxxB-
C1
(220~240 VAC): A2, A3
•
VS p III xxx xxxxB-
C2
(24 VAC/VDC): A1, A2
UL Compliant Installation
For models VS p III 184 to VS p III 580 to be UL compliant, supplementary or
branch overcurrent protection must be used on the control circuit supply (A1, A2,
A3), in accordance with the electrical code applicable at the installation location.