21
VersiStart p III
•
Circuit breakers – High fault short circuit current
Suitable for use on a circuit capable of delivering not more than 65,000 rms
symmetrical amperes, 480 VAC maximum, when protected by circuit breaker
models noted in ##4, ##5 or ##6.
Model
Nominal
Rating (A)
Breaker 1: Eaton
(rating, A)
Breaker 2: GE
(rating, A)
Breaker 3: LS
(rating, A)
1
##4
##5
##6
VS p III 24
24
HFD3030 (30 A)
UTS150H-xxU-040
(40 A)
VS p III 42
42
HFD3050 (50 A)
SELA36AT0060
(60 A)
UTS150H-xxU-050
(50 A)
VS p III 52
52
HFD3060 (60 A)
UTS150H-xxU-060
(60 A)
VS p III 64
64
HFD3100
(100 A)
SELA36AT0150
(150 A)
UTS150H-xxU-100
(100 A)
VS p III 69
69
VS p III 105
105
HFD3125
(125 A)
UTS150H-xxU-125
(125 A)
VS p III 115
120
VS p III 135
135
HFD3150
(150 A)
UTS150H-xxU-150
(150 A)
VS p III 184
184
HFD3250
(250 A)
SELA36AT0250
(250 A)
UTS150H-xxU-250
(250 A)
VS p III 200
225
VS p III 229
229
VS p III 250
250
HFD3300
(300 A)
SELA36AT0400
(400 A)
UTS150H-xxU-300
(300 A)
VS p III 352
352
HFD3400
(400 A)
SELA36AT0600
(600 A)
UTS150H-xxU-400
(400 A)
VS p III 397
397
VS p III 410
410
HFD3600
(600 A)
UTS150H-xxU-600
(600 A)
VS p III 550
550
UTS150H-xxU-800
(800 A)
VS p III 580
580
UTS150H-NG0-800
1
For LS breakers, xx represents FM, FT or AT.
Содержание VersiStart p III 105
Страница 108: ......