2
018-
04
62
HART Multiplexer System KFD*-HM*-16
Operation
7
Operation
7.1
Device Functions
The software functions described in this chapter are usually integrated in the
operating software of the process control system, i. e., the software functions are generally
not
enabled or disabled via the described HART commands. Instead, they exist in the functions
(menu commands) of the operating software that take on these processes. Nevertheless, the
underlying HART commands are described because the functions may have different names
in the individual user interfaces and the underlying basic functions may not always be apparent
from the name. For a list of the commands supported see chapter 9.1.
All Functions at a Glance
The following list shows all the functions of the multiplexer master at a glance:
•
16 channels, expandable up to 256 channels by connecting up to 15 multiplexer slaves
•
Up to 7936 signal loops per RS-485 interface
•
Automatic search of all existing HART-compatible field devices (scan)
•
Switchable, independent, cyclical querying of the HART variables (command caching)
•
Acts as the primary or secondary multiplexer master
•
Fast RS-485 interface (multidrop) with up to 56700 baud
•
Integrated modem
•
Removable terminals
•
Power supply via Power Rail
•
Approved for Zone 2
Danger!
Explosion hazard from live wiring of circuits
If you connect or disconnect energized circuits in a potentially explosive atmosphere,
sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized circuits in the absence of a potentially explosive
atmosphere.
Danger!
Explosion hazard from sparking when using operating elements
Using operating elements in a potentially explosive atmosphere can cause sparks that can
ignite the surrounding atmosphere.
Only use operating elements (e. g., switch, slider, button, etc.) in the absence of a potentially
explosive atmosphere.
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...