Results of the HART Scan
As the result of the HART scan, a table is output containing the following information about the
field devices found:
Loop
Device data
Match result
Assigned DTM
DTM action
Apply
Slave and loop
address of the
field device
Name and data
of the
field device
Specifies
whether the
HART scan
wizard has
found a suitable
DTM
Suggested DTM Specifies what
the HART scan
wizard will do
with the
selected DTM
Select this
check box to
apply the
changes for this
field device
Table 6.1
Results table for the HART scan
Match result
Explanation
Single green checkmark
The assigned DTM matches the device exactly.
Two green checkmarks
There are several DTMs, that match the
field device data.
Individual gray checkmark
The Generic HART DTM has been assigned to the
device as no device-specific DTM has been found.
Yellow warning triangle
The assigned DTM does not match the device.
Table 6.2
Explanation of the match result
DTM action
Explanation
Yellow star
No DTM has been assigned to the field device yet.
A new DTM will be created in the project tree.
Pen
The DTM previously assigned to the device will be
replaced by the new DTM selected.
Red cross
The field device for this DTM that exists in the project
is missing. The DTM will be removed from the
project tree.
Table 6.3
Explanation of the DTM action
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...