
HART Multiplexer System KFD*-HM*-16
Product Specifications
201
8-04
9
2.2.2
HART Multiplexer Slave KFD0-HMS-16
A maximum of 16 analog field devices can be connected to the multiplexer slave. The device
can only be used in conjunction with the HART multiplexer master KFD2-HMM-16.
The device is supplied with power by the multiplexer master via the 14-pin ribbon cable.
The device is connected with the multiplexer master and additional multiplexer slaves
via a 14-pin ribbon cable. The device has a 14-pin IDC socket on the bottom of the device for
this purpose.
The device is connected to the termination board via a 26-pin ribbon cable.
The device has a 26-pin IDC socket on the front of the device for this purpose.
The device address is set using a rotary switch. You can assign addresses 1 to 15.
The address 0 is reserved for the multiplexer master and may therefore not be used. If several
multiplexer slaves are connected to the multiplexer master, different addresses must
be assigned. The sequence is irrelevant.
Figure 2.2
Assembly of the KFD0-HMS-16 HART multiplexer slave
KFD0-HMS-16
1
26
Rotary switch
26 pin
connector
14 pin
connector
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...