HART Multiplexer System KFD*-HM*-16
Commissioning
201
8-04
29
5.2.2
DIP Switch Settings
The device is equipped with 8 DIP switches on the front.
DIP switch 1 is used for device testing by the manufacturer and must therefore always be in
the
off
position.
DIP switches 2 and 3 determine the baud rate of the RS-485 interface.
DIP switches 4 to 8 define the RS-485 address. A value assigned to each of the DIP switches.
The address is calculated from the sum of the values.
Danger!
Explosion hazard from sparking when using operating elements
Using operating elements in a potentially explosive atmosphere can cause sparks that can
ignite the surrounding atmosphere.
Only use operating elements (e. g., switch, slider, button, etc.) in the absence of a potentially
explosive atmosphere.
DIP switch
1
Meaning
Position
Off
Normal state
Table 5.1
DIP switch
2
3
Meaning
Position
Off
Off
9600 baud
Off
On
19200 baud
On
Off
38400 baud
On
On
57600 baud
Table 5.2
DIP switch
4
5
6
7
8
Meaning
Position
On
Off
Off
Off
Off
Value 16
Off
On
Off
Off
Off
Value 8
Off
Off
On
Off
Off
Value 4
Off
Off
Off
On
Off
Value 2
Off
Off
Off
Off
On
Value 1
Example
Off
On
On
Off
On
Address = 8 + 4 +1 = 13
Table 5.3
Note!
Briefly disconnect the device from the power supply to apply the values set using
the DIP switches.
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...