ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
Recommended Clearances
(cont.)
OUTDOOR INSTALLATION
VENTING GUIDELINES
Chec
k local b
uilding codes
for setbac
k requirements
.
Force
Air Inlet
Property Line
4’
(1.2m)
4’
(1.2m)
3’
(0.9m)
ROOF OVERHANG
Building
From window
or door
SIDE VIEW
Building
From building wall
Exhaust Grill
(Vent)
12"
(30.5cm)
Roof Overhang
4’
(1.2m)
4’
(1.2m)
12"
(30.5cm)
Must be at least 3 ft. (0.9 m) above any forced
air inlet located within a 10 ft. (3.5 m) radius.
Vent Termination:
Must be located 12 in. (30.5 cm) away from the building
wall and the following distances away from any building
wall openings, included but not limited to vented eaves,
doors, windows, gravity air inlet:
4 ft. (1.2 m) below,
4 ft. (1.2 m) horizontally
Figure 3:
Vent Clearances