ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide 

Professional Maintenance and Service

The maximum heat output and efficiency of a heater is 
dependent upon the quality and performance of the major 
components used. Equally important are the environmental 
conditions (for example, air temperature, humidity, water 
temperature, and wind). 

To maintain maximum performance and efficiency, keep 
the air coil clean from dirt and debris. It is recommended 
to clean your air coil once a year by flushing the coil with 
compressed air or hosing off the coil with a garden hose. 

Care should be taken to not bend the coil fins as this will 
restrict the airflow and lower your heater performance. 
Compressed air can also damage the heater coil.  DO 
NOT USE A PRESSURE CLEANER ON THE UNIT.

The heater should be maintained at least once a year by 
qualified personnel to maintain maximum performance 
and efficiency. The unit should be powered off during 
maintenance. 

Winterizing

In areas where freezing temperatures occur, you should 
protect your pump, filter, and heater from the elements. 
Perform the following steps to completely drain the heater.

1.  Turn off the electrical power to the heater at the main 

breaker panel. 

2.  Close main gas control valve and manual gas valve.

3.  Shut off the water supply to the heater. 

4.  Drain all water from the heater system.

5.  Disconnect  the  water  inlet  and  outlet  unions  from  the 

system plumbing.

6.  If the heater is below pool water level, be sure to 

close the isolation valves to prevent from draining the 
pool. Isolation valves are not required and should not 
be used on heaters installed above pool water level, 
except when needed for winterization valves.

7.  Remove the black drain plug located to the right of the 

High Limit Switch (HLS). 

 

Alternatively, disconnect the water management 
system at the two internal unions and quick release 
clips to partially drain, then reassemble.

8.  Use a blower, connected to the outlet of the heater, to 

remove all remaining water from the heater.

9.  Cover air inlet grate with a plastic bag to prevent bugs, 

leaves, etc., from getting into the heater.

10.  Remove the hose barb from the condensate 

neutralizer cartridge outlet and drain all water from the 
cartridge and connected tubing.

Spring Start Up

If your heater has been winterized, perform the following 
steps when starting the system in the Spring: 

1.  Uncover the heater and inspect the top and sides for 

any debris or structural problems. 

2.  Connect the water inlet and outlet unions to the  

system plumbing. Ensure they are connected correctly 
and that there are no water leaks.

3.  Place the drain plug back into the port in the water 

management assembly.

4.  Reconnect the condensate neutralizer cartridge hose.

5.  Turn on the electrical power to the heater at the main 

breaker panel.

6.  Before starting the heater, circulate water through the 

heater for several minutes until all air no

ises stop. 

See 

also 

Pre-Startup

 (page 21) and 

General Maintenance

 

(page 33).

Separation  hazard.  Purging  the  system  with 
compressed air can cause components to separate, 

with risk of severe injury or death to anyone nearby. Use only a low pressure 
(below 5 PSI or 35 kPa), high volume blower when air purging the heater.

Failure to winterize could cause damage to the heater 
and will void the warranty.

Water trapped in the heat exchanger can result in freeze 
damage to the exchanger or headers. Freeze damage 

is specifically not covered by the warranty.

When  starting  the  heater  for  the  swimming  season 
with  a  water  temperature  below  50°  F  (10°  C),  the 

heater may be used to heat the water; however, make sure that the heater 
operates  continuously  until  the  water  temperature  reaches  the  heater’s 
minimum setting of 68° F (20° C). During cold weather, if there is no danger 
of freezing, operate the filter pump continuously even if the heater is not 
operating. If air temperatures are expected to drop below freezing (32° F/0° 
C), shut down the heater and winterize it. 

Содержание ULTRATEMP ETi 220

Страница 1: ...ENGLISH INSTALLATION AND USER S GUIDE HYBRID HEATER IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS ULTRATEMP ETi ESPA OL FRAN AIS ENGLISH...

Страница 2: ...to EasyTouch via Heater Spade Terminals Connecting to EasyTouch via RS 485 Connector Pin Configuration for Heater Control Board to EasyTouch Connecting EasyTouch to the Heater Operating the Heater Swi...

Страница 3: ...the 100 F 38 C maximum rule 4 Before entering the spa or hot tub the user should check the water temperature with an accurate thermometer Spa or hot tub thermostats may err in regulating water temper...

Страница 4: ...rbon monoxide detectors must be periodically inspected for proper operation so as to insure continued safety Broken or malfunctioning carbon monoxide detectors must be replaced immediately This heater...

Страница 5: ...ral purpose water heater 4 The heater should be located in an area where leakage of the heater or connections will not result in damage to the area adjacent to the heater or to the structure When such...

Страница 6: ...acket 4 Electric cutout switch that will interrupt all power to the unit This switch must be within line of sight of the heater Check local codes for requirements 5 Watertight conduit to run the elect...

Страница 7: ...oth the plumbing and control panel side of the heater This will provide necessary room for servicing 2 At least 12 inches 305 mm of clearance must be available on all the other sides of the heater to...

Страница 8: ...SIDE VIEW Building From building wall Exhaust Grill Vent 12 30 5cm Roof Overhang 4 1 2m 4 1 2m 12 30 5cm Must be at least 3 ft 0 9 m above any forced air inlet located within a 10 ft 3 5 m radius Vent...

Страница 9: ...r drains and or pipes particularly those that are metal Ensure that the drain drainpipe and anything that will come in contact with the condensate can withstand the acidity Damage caused by failure to...

Страница 10: ...location on the equipment pad 2 Place the clamps at the base of the heater in the eight 8 locations shown in Figure 5 Note Bolts and washers are not included with the heater The installer must provid...

Страница 11: ...Install a chemical resistant one way check valve between the heater and the chemical feeder to prevent back siphoning through the heater when the pump is off Note If the heater is plumbed in backward...

Страница 12: ...ressure Relief Valve Kit P N 475943 complying with the ANSI ASME Boiler and Pressure Vessel Code having a capacity equal to the Btu hr rating of the heater Note The relief pressure of the valve MUST N...

Страница 13: ...um 3 PVC Pipe 2 PVC Pipe Flow Meter To Pool 3 Ball Valve Bypass Check Valves are optional on heater inlets but will help for system balancing 36 914 mm 2 PVC Pipe 2 PVC Pipe 2 PVC Pipe 3 PVC Pipe 3 PV...

Страница 14: ...e plumbing system On some installations the piping from the heater to the pool is very short The back pressure could be too low to trigger the pressure switch If this happens install a directional fit...

Страница 15: ...ipe as this may cause damage to the gas valve which may result in heater failure The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that...

Страница 16: ...lve Risk of explosion if a unit burning propane gas is installed in a pit or other low spot Propane is heavier than air Do not install the heater using propane in pits or other locations where gas mig...

Страница 17: ...Remove the long side service panel of the heater cabinet There is no need to remove the star head screws 2 Remove the short side service panel to the heater electrical compartment 3 Remove the sheet m...

Страница 18: ...14 ULTRATEMP ETI Hybrid Heater Installation and User s Guide Wiring Diagram Input Side...

Страница 19: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 15 Wiring Diagram Output Side P N 476088 B 4 10 18 ENGLISH...

Страница 20: ...s 1 Turn off the power to both the remote pool spa control system and the heater 2 Remove the side panel of the heater cabinet you do not need to remove the star head screw at the top left corner 3 Re...

Страница 21: ...Run a UL approved conductor cable from the heater to the Load Center 5 Route the cable up through the low voltage raceway located on the left of the Load Center to the Personality Board see image belo...

Страница 22: ...tem power before making any connections 2 Unlatch the EasyTouch load center front door spring latches and open the front door 3 Remove the cover panel screws securing the high voltage cover panel and...

Страница 23: ...ace the side panel 8 Restore power to the heater and the EasyTouch control system 9 Press the MENU SELECT button to scroll to the Remote Mode screen Toggle the selection by pressing one of the arrows...

Страница 24: ...he cost of operating your heater without sacrificing performance 1 The American Red Cross recommends a maximum water temperature of 83 86 F 28 3 30 C Use an accurate pool thermometer A difference of 3...

Страница 25: ...ore details and explanations regarding heater features and programming Pre Startup 1 This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner D...

Страница 26: ...bout 15 seconds the burner should fire When operating for the first time the burner may not fire on the first try because of air in the gas line If it does not fire at first push the ON OFF button wai...

Страница 27: ...e water pressure switch refer back to page 10 Water Pressure Switch Adjustment Turn the star wheel on the switch clockwise to raise setting heater below the pool level and counterclockwise to lower th...

Страница 28: ...loat Switch CFS The Float Switch CFS is a sensing application that shuts down the heater once the condensate level exceeds the permitted level in the condensate container Ignition Module Operation The...

Страница 29: ...an RS 485 connected IntelliFlo pump when the heater is attempting to heat to its set point Suction Temperature Screen Shows the suction line temperature of the refrigerant This screen only appears if...

Страница 30: ...T ___ Remote Mode Relay In Relay Remote Mode operation the heater is started and stopped by remote relays which are connected to the remote POOL COMMON and SPA quick connect terminals on the back of t...

Страница 31: ...h an RS 485 connected IntelliFlo or IntelliPro pump to ensure water is flowing through the heater when water heating is required Note This feature requires that an RS 485 communication cable be connec...

Страница 32: ...message for two 2 minutes FIVE ALARMS Indicates that five 5 faults have occurred in one 1 hour This fault will automatically reset in one 1 hour or can be manually reset by pressing the ON OFF button...

Страница 33: ...using the UP and DOWN arrows Defrost Screen Allows the user to Enable Disable Defrost feature Heat Pump Input Screen and Output Screen Diagnostic displays showing the status of the input sensors and...

Страница 34: ...e the heater compressor stops The heater evaporator fan will continue to run and will draw air over the evaporator fins for about 15 minutes If the refrigerant sensor detects a temperature above the d...

Страница 35: ...NTY CYCLES number of cycles over the lifespan of the unit Press the UP and DOWN arrows to scroll through the Timers and Counters The last screen provides an option to reset the Run Time Log Time and C...

Страница 36: ...of your pool water is available from your local pool supply store If pH becomes too high over alkaline it has these effects 1 Reduces the ability of chlorine to destroy bacteria and algae 2 Water beco...

Страница 37: ...e the heat pump is in operation The heater base is designed to allow the condensation to exit through the bottom drain port when the unit is running The condensation will increase as the outdoor air h...

Страница 38: ...to partially drain then reassemble 8 Use a blower connected to the outlet of the heater to remove all remaining water from the heater 9 Cover air inlet grate with a plastic bag to prevent bugs leaves...

Страница 39: ...80W Current Amp 80A 63RH 80W Capacity Btu h 50A 63RH 80W COP 50A 63RH 80W Power Input KW 50A 63RH 80W Current Amp 50A 63RH 80W Min Circuit Ampacity Amp 148 4 150 Electrical Supply Voltage Requirement...

Страница 40: ...s closely matched by the ambient and water flow conditions 0 1 2 3 4 5 6 7 8 9 10 11 12 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure Drop psi Water Flow gpm UltraTemp ETI Pressure Drop Curve Pres...

Страница 41: ...If shows open replace thermistor If good replace control board SUCTION TH SHORT Alarm Defrost refrigerant temperature sensor circuit is shorted Bad thermistor or bad control board Use the 10k ohm resi...

Страница 42: ...ed Call for professional servicing LOW REFRIG Alarm Refrigerant low pressure switch is open 1 Low refrigerant in system Call for professional servicing 2 Air and water temperatures too cold to operate...

Страница 43: ...nector pin 1 and ignition control module terminal F2 On call for heat if blower starts but shuts off within 30 seconds refer to Faulty Air Flow Switch or Switch Wiring troubleshooting below 6 Faulty a...

Страница 44: ...ore attempting to Troubleshoot Electrical Box 1 Heater condensate drain hose restriction Verify proper hose routing from heater base Ensure there are no loops kinks or elevated portions between hose e...

Страница 45: ...heater Unit ON and Set Temperature is above Actual but Unit is not heating No Alarms Heater is in the five minute safety delay and Compressor has not started Faulty Compressor Faulty Capacitor Compre...

Страница 46: ...ue Contact certified electrician BURNER TROUBLESHOOTING Loud high pitched whine Flame is too rich Verify pressure tap between gas valve and blower inlet See page 11 and verify that the gas regulator s...

Страница 47: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 43 REPLACEMENT PARTS Heater Parts Breakdown REFRIGERATION OUTER SHELL p 44 GAS SYSTEM p 45 ELECTRICAL p 46 PLUMBING p 47 ENGLISH...

Страница 48: ...ck 9 475230Z Compressor Blanket 10 475948Z Titanium Heat Exchanger Tie Down Bracket 11 475949Z Titanium Heat Exchanger 12 473735Z Compressor ZP70 Item Part Description 13 473121 Drier Single Direction...

Страница 49: ...st Replacement Kit 25 475877 Exhaust Gasket Kit 2 Pieces 26 475989 Gas Engine Spark Electrodes 27 475898 Burner Assembly 28 462023 Flame Sensor Item Part Description 29 475897Z Heat Exchanger 100K BTU...

Страница 50: ...Wire Harness Heat Pump Inputs 35 475930Z Wire Harness Outputs 36 475926Z Wire Harness Spark Plugs 37 475931Z Wire Harness Gas Blower 38 473155 Transformer 39 475933Z Ignition Control Module Item Part...

Страница 51: ...75941 Switch Automatic Gas Shutoff 140 F 56 475955Z Switch High Limit 127 F 57 471566 Probe Thermistor Water Temperature 58 473381 Union PVC 2in 59 475953Z QRC Clip 60 98218900 Drain Plug 1 4 NPT Item...

Страница 52: ...essly noted names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Po...

Отзывы: