ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide 

Using the Operator Menus

Starting and Stopping the Heater 

The UltraTemp ETi™ Hybrid Heater is started and 
stopped with the ON/OFF button.

1.  Starting - With power supplied to the heater, press 

the ON/OFF button to start the heater. The ON 
light should be lit.

2.  Stopping -  Press the ON/OFF button to stop the 

heater; the ON light will turn off. The screen shown 
below will be displayed temporarily.

Changing the Set Point (Temperature)

The control board has two independently adjustable 
temperature set points. One is for the pool temperature 
control and the other is for the spa temperature control. 
The active mode of operation (Pool or Spa) is defined 
as the “active” set point. 

1.  Press the MENU SELECT button repeatedly until 

the associated run screen is displayed. Press the 
UP or DOWN arrows to adjust the pool or spa 
temperature set point. 

 

SET= ___  - Set point

 

ACT= ___  - Actual measured water temperature

2.  The screen automatically returns to the active run 

screen after 15 seconds of keypad inactivity. 

Efficiency Mode Selection

These heaters can be setup to operate in any one of four 
modes (Heat Pump Only, Gas Only, Hybrid or Dual).

In Hybrid mode, the heater automatically switches 
between heating the water by means of heat pump or 
gas heating in order to maximize efficiency. In Dual mode 
the heat pump functionality and gas heater will work in 
tandem to heat the pool/spa.

1.  Press the MENU SELECT button repeatedly until the 

Mode Selection screen displays. 

2.  Press the UP or DOWN arrows to scroll through the 

HEAT PUMP, GAS, HYBRID and DUAL options. The 
last option shown on the display becomes active.

POOL

HT PUMP / HYBRID / DUAL / GAS

SET=___ ACT=___

Remote Mode - Relay

In Relay Remote Mode operation, the heater is started 
and stopped by remote relays which are connected to 
the remote POOL, COMMON and SPA quick connect 
terminals on the back of the control board. 
When conductivity is provided between the POOL 
and COMMON terminals or the SPA and COMMON 
terminals, the heater will start. All other features and 
functions (except for the Heater Timer) are still active. 
The heater will not heat above 104°F (40°C).

To activate the Relay Remote Mode:

1.  Press MENU SELECT repeatedly until the Remote  

Mode screen is displayed. Once displayed, press 
the UP or DOWN arrows to select RELAY. The last 
option shown on the display becomes active.

REMOTE MODE

RELAY

HEATER RUNTIME

REMAINING = NONE

Heater Timer 

This feature is an adjustable timer to allow the heater to 
run for a predetermined amount of time (green light ON) 
and then turn OFF (green light OFF).
During the selected time frame, the green light is 
ON and the heater functions in the normal mode of 
operation. When time expires the green light turns OFF 
and the heater turns off. Countdown time is in hours 
and minutes.

To activate the Heater Timer:

1.  Press MENU SELECT repeatedly until the Heater 

Timer screen is displayed.

2.  Press UP or DOWN arrows to set the amount 

of time (range of 10 minutes to 99 hours). Timer 
adjusts in increments of 10 minutes.

 

If the heater is not already on, setting the timer will 
activate and start the heater.

3.  The user can also change the time while it is active 

using the arrow buttons, but only if Remote mode 
is OFF. Setting Remote Mode to RELAY or RS-485 
disables the Heater Timer at the control panel.

4.  Any RS-485 communication received will reset the 

timer to zero. The RS-485 overrides the Heater 
Timer operation.

5.  The timer can be disabled by pressing the DOWN 

arrow and MODE buttons at the same time, or by 
pressing the ON/OFF button.

PENTAIR AQUATICS

HEATER OFF

Содержание ULTRATEMP ETi 220

Страница 1: ...ENGLISH INSTALLATION AND USER S GUIDE HYBRID HEATER IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS ULTRATEMP ETi ESPA OL FRAN AIS ENGLISH...

Страница 2: ...to EasyTouch via Heater Spade Terminals Connecting to EasyTouch via RS 485 Connector Pin Configuration for Heater Control Board to EasyTouch Connecting EasyTouch to the Heater Operating the Heater Swi...

Страница 3: ...the 100 F 38 C maximum rule 4 Before entering the spa or hot tub the user should check the water temperature with an accurate thermometer Spa or hot tub thermostats may err in regulating water temper...

Страница 4: ...rbon monoxide detectors must be periodically inspected for proper operation so as to insure continued safety Broken or malfunctioning carbon monoxide detectors must be replaced immediately This heater...

Страница 5: ...ral purpose water heater 4 The heater should be located in an area where leakage of the heater or connections will not result in damage to the area adjacent to the heater or to the structure When such...

Страница 6: ...acket 4 Electric cutout switch that will interrupt all power to the unit This switch must be within line of sight of the heater Check local codes for requirements 5 Watertight conduit to run the elect...

Страница 7: ...oth the plumbing and control panel side of the heater This will provide necessary room for servicing 2 At least 12 inches 305 mm of clearance must be available on all the other sides of the heater to...

Страница 8: ...SIDE VIEW Building From building wall Exhaust Grill Vent 12 30 5cm Roof Overhang 4 1 2m 4 1 2m 12 30 5cm Must be at least 3 ft 0 9 m above any forced air inlet located within a 10 ft 3 5 m radius Vent...

Страница 9: ...r drains and or pipes particularly those that are metal Ensure that the drain drainpipe and anything that will come in contact with the condensate can withstand the acidity Damage caused by failure to...

Страница 10: ...location on the equipment pad 2 Place the clamps at the base of the heater in the eight 8 locations shown in Figure 5 Note Bolts and washers are not included with the heater The installer must provid...

Страница 11: ...Install a chemical resistant one way check valve between the heater and the chemical feeder to prevent back siphoning through the heater when the pump is off Note If the heater is plumbed in backward...

Страница 12: ...ressure Relief Valve Kit P N 475943 complying with the ANSI ASME Boiler and Pressure Vessel Code having a capacity equal to the Btu hr rating of the heater Note The relief pressure of the valve MUST N...

Страница 13: ...um 3 PVC Pipe 2 PVC Pipe Flow Meter To Pool 3 Ball Valve Bypass Check Valves are optional on heater inlets but will help for system balancing 36 914 mm 2 PVC Pipe 2 PVC Pipe 2 PVC Pipe 3 PVC Pipe 3 PV...

Страница 14: ...e plumbing system On some installations the piping from the heater to the pool is very short The back pressure could be too low to trigger the pressure switch If this happens install a directional fit...

Страница 15: ...ipe as this may cause damage to the gas valve which may result in heater failure The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that...

Страница 16: ...lve Risk of explosion if a unit burning propane gas is installed in a pit or other low spot Propane is heavier than air Do not install the heater using propane in pits or other locations where gas mig...

Страница 17: ...Remove the long side service panel of the heater cabinet There is no need to remove the star head screws 2 Remove the short side service panel to the heater electrical compartment 3 Remove the sheet m...

Страница 18: ...14 ULTRATEMP ETI Hybrid Heater Installation and User s Guide Wiring Diagram Input Side...

Страница 19: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 15 Wiring Diagram Output Side P N 476088 B 4 10 18 ENGLISH...

Страница 20: ...s 1 Turn off the power to both the remote pool spa control system and the heater 2 Remove the side panel of the heater cabinet you do not need to remove the star head screw at the top left corner 3 Re...

Страница 21: ...Run a UL approved conductor cable from the heater to the Load Center 5 Route the cable up through the low voltage raceway located on the left of the Load Center to the Personality Board see image belo...

Страница 22: ...tem power before making any connections 2 Unlatch the EasyTouch load center front door spring latches and open the front door 3 Remove the cover panel screws securing the high voltage cover panel and...

Страница 23: ...ace the side panel 8 Restore power to the heater and the EasyTouch control system 9 Press the MENU SELECT button to scroll to the Remote Mode screen Toggle the selection by pressing one of the arrows...

Страница 24: ...he cost of operating your heater without sacrificing performance 1 The American Red Cross recommends a maximum water temperature of 83 86 F 28 3 30 C Use an accurate pool thermometer A difference of 3...

Страница 25: ...ore details and explanations regarding heater features and programming Pre Startup 1 This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner D...

Страница 26: ...bout 15 seconds the burner should fire When operating for the first time the burner may not fire on the first try because of air in the gas line If it does not fire at first push the ON OFF button wai...

Страница 27: ...e water pressure switch refer back to page 10 Water Pressure Switch Adjustment Turn the star wheel on the switch clockwise to raise setting heater below the pool level and counterclockwise to lower th...

Страница 28: ...loat Switch CFS The Float Switch CFS is a sensing application that shuts down the heater once the condensate level exceeds the permitted level in the condensate container Ignition Module Operation The...

Страница 29: ...an RS 485 connected IntelliFlo pump when the heater is attempting to heat to its set point Suction Temperature Screen Shows the suction line temperature of the refrigerant This screen only appears if...

Страница 30: ...T ___ Remote Mode Relay In Relay Remote Mode operation the heater is started and stopped by remote relays which are connected to the remote POOL COMMON and SPA quick connect terminals on the back of t...

Страница 31: ...h an RS 485 connected IntelliFlo or IntelliPro pump to ensure water is flowing through the heater when water heating is required Note This feature requires that an RS 485 communication cable be connec...

Страница 32: ...message for two 2 minutes FIVE ALARMS Indicates that five 5 faults have occurred in one 1 hour This fault will automatically reset in one 1 hour or can be manually reset by pressing the ON OFF button...

Страница 33: ...using the UP and DOWN arrows Defrost Screen Allows the user to Enable Disable Defrost feature Heat Pump Input Screen and Output Screen Diagnostic displays showing the status of the input sensors and...

Страница 34: ...e the heater compressor stops The heater evaporator fan will continue to run and will draw air over the evaporator fins for about 15 minutes If the refrigerant sensor detects a temperature above the d...

Страница 35: ...NTY CYCLES number of cycles over the lifespan of the unit Press the UP and DOWN arrows to scroll through the Timers and Counters The last screen provides an option to reset the Run Time Log Time and C...

Страница 36: ...of your pool water is available from your local pool supply store If pH becomes too high over alkaline it has these effects 1 Reduces the ability of chlorine to destroy bacteria and algae 2 Water beco...

Страница 37: ...e the heat pump is in operation The heater base is designed to allow the condensation to exit through the bottom drain port when the unit is running The condensation will increase as the outdoor air h...

Страница 38: ...to partially drain then reassemble 8 Use a blower connected to the outlet of the heater to remove all remaining water from the heater 9 Cover air inlet grate with a plastic bag to prevent bugs leaves...

Страница 39: ...80W Current Amp 80A 63RH 80W Capacity Btu h 50A 63RH 80W COP 50A 63RH 80W Power Input KW 50A 63RH 80W Current Amp 50A 63RH 80W Min Circuit Ampacity Amp 148 4 150 Electrical Supply Voltage Requirement...

Страница 40: ...s closely matched by the ambient and water flow conditions 0 1 2 3 4 5 6 7 8 9 10 11 12 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure Drop psi Water Flow gpm UltraTemp ETI Pressure Drop Curve Pres...

Страница 41: ...If shows open replace thermistor If good replace control board SUCTION TH SHORT Alarm Defrost refrigerant temperature sensor circuit is shorted Bad thermistor or bad control board Use the 10k ohm resi...

Страница 42: ...ed Call for professional servicing LOW REFRIG Alarm Refrigerant low pressure switch is open 1 Low refrigerant in system Call for professional servicing 2 Air and water temperatures too cold to operate...

Страница 43: ...nector pin 1 and ignition control module terminal F2 On call for heat if blower starts but shuts off within 30 seconds refer to Faulty Air Flow Switch or Switch Wiring troubleshooting below 6 Faulty a...

Страница 44: ...ore attempting to Troubleshoot Electrical Box 1 Heater condensate drain hose restriction Verify proper hose routing from heater base Ensure there are no loops kinks or elevated portions between hose e...

Страница 45: ...heater Unit ON and Set Temperature is above Actual but Unit is not heating No Alarms Heater is in the five minute safety delay and Compressor has not started Faulty Compressor Faulty Capacitor Compre...

Страница 46: ...ue Contact certified electrician BURNER TROUBLESHOOTING Loud high pitched whine Flame is too rich Verify pressure tap between gas valve and blower inlet See page 11 and verify that the gas regulator s...

Страница 47: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 43 REPLACEMENT PARTS Heater Parts Breakdown REFRIGERATION OUTER SHELL p 44 GAS SYSTEM p 45 ELECTRICAL p 46 PLUMBING p 47 ENGLISH...

Страница 48: ...ck 9 475230Z Compressor Blanket 10 475948Z Titanium Heat Exchanger Tie Down Bracket 11 475949Z Titanium Heat Exchanger 12 473735Z Compressor ZP70 Item Part Description 13 473121 Drier Single Direction...

Страница 49: ...st Replacement Kit 25 475877 Exhaust Gasket Kit 2 Pieces 26 475989 Gas Engine Spark Electrodes 27 475898 Burner Assembly 28 462023 Flame Sensor Item Part Description 29 475897Z Heat Exchanger 100K BTU...

Страница 50: ...Wire Harness Heat Pump Inputs 35 475930Z Wire Harness Outputs 36 475926Z Wire Harness Spark Plugs 37 475931Z Wire Harness Gas Blower 38 473155 Transformer 39 475933Z Ignition Control Module Item Part...

Страница 51: ...75941 Switch Automatic Gas Shutoff 140 F 56 475955Z Switch High Limit 127 F 57 471566 Probe Thermistor Water Temperature 58 473381 Union PVC 2in 59 475953Z QRC Clip 60 98218900 Drain Plug 1 4 NPT Item...

Страница 52: ...essly noted names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Po...

Отзывы: