ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
29
Service Menu Tree Guide
(Press UP and DOWN Arrows Simultaneously)
Navigating the Service Menu Screens
Press the UP and DOWN arrows simultaneously. If no activity
is detected after 15 seconds, the display will return to the main
screen.
Language Selection
Displays the language selected. Select either English, Spanish
or French using the UP and DOWN arrows.
Software Revision
Displays the software revision level loaded on the control board.
Intell Address
Heater RS-485 Communications Address which must match
the address used in the EasyTouch automation controller
being communicated with. Adjustable from 1 to 16 using the
UP and DOWN arrows.
Start Delay
Displays the time period between heater start cycles. Adjustable
from 0 to 5 minutes using the UP and DOWN arrows.
Eco-Time
Displays the period of time the heat pump will attempt to reach
an active set point before the gas heater activates. Adjustable
from 1 to 6 hours
using the UP and DOWN arrows.
Boost Temperature
Displays the temperature difference allowed between incoming
water temperature and active set point. If the temperature
difference exceeds this setting the gas heater will activate.
Adjustable from 5-10 degrees
using the UP and DOWN arrows
.
Temperature Scale
Determines if the water temperature actual reading and set
point is displayed in degrees Fahrenheit or Celsius. Adjusted
between Fahrenheit and Celsius using the UP and DOWN
arrows.
Temp Offset
Adjusts the measured water temperature up or down to allow
the operator to match the heater’s displayed temperature to
a remote temperature monitoring device. The offset can be
varied from -2 to +2 using the UP and DOWN arrows.
Defrost Screen
Allows the user to Enable/Disable Defrost feature.
Heat Pump Input Screen and Output Screen
Diagnostic displays showing the status of the input sensors
and output devices. The number one (1) is displayed when the
associated input/output is on and zero (0) is displayed when
the associated input/output is off.
Gas Input Status Screens
Diagnostic displays showing the status of gas-related input
sensors. The number one (1) is displayed when the associated
input is on and zero (0) is displayed when the associated
input is off.
Temperature Log and Run Time Counters
These screens display a list of compressor, fan and valve run
times, and a history of measured water temperatures. This
information is provided so the user can easily track performance
and troubleshoot issues.
Exit Set Up
Pressing the MODE button while this screen is displayed
returns the display to the Efficiency Mode Screen.
HEAT PUMP INPUT STATUS
WF = WATER FLOW SWITCH
HP = HIGH REFRIGERANT
PRESSURE SWITCH
LP = LOW REFRIGERANT
PRESSURE SWITCH
PL = POOL REMOTE
SP = SPA REMOTE
1
*
LANGUAGE - IDIOMA - LANGUE
ENGLISH / ESPANOL / FRANCAIS
VERSION SOFTWARE
REV. ____
TEMPERATURE SCALE
FAHRENHEIT / CELSIUS
PRESS MODE
TO EXIT SETUP
WF HP LP PL SP
1 1 1 0 0
FAN COMP GAS REV
1 1 1 0
DEFROST
ENABLE / DISABLE
WATER TEMP OFFSET
OFFSET = -2 TO +2
START DELAY
TIME = 0 - 5 MINS
1
2
RUN TIMES/COUNTS
OR TO VIEW
TEMP. RECORD
HOUR # ___ ___°F
INTELL ADDRESS
ADDRESS = 1-16
ECO TIME
TIME = 1 - 6 HRS
BOOST TEMPERATURE
TEMP = 5 - 10
CFS TF HLS
1 1 1
AFS VAL AGS
1 1 1
3
4
*
OUTPUT STATUS
FAN - FAN
COMP - COMPRESSOR
GAS - GAS HEAT
REV - REVERSING VALVE
2
GAS INPUT STATUS
CFS - CONDENSATE FLOAT
SWITCH
TF - THERMAL FUSE
HLS - HIGH LIMIT SWITCH
3
GAS INPUT STATUS (cont.)
AFS - AIR FLOW SWITCH
VAL - GAS VALVE
AGS - AUTO GAS SHUTOFF
4
NOTE:
These settings
are only active when
Efficiency Mode is set to
“Hybrid”
*
1
2
3
4
ENGLISH