ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide 

Solar Installations

The UltraTemp ETi™ Hybrid Heater can be used in 
combination with other heating schemes such as solar. All 
heat sources must be plumbed in series to work correctly 
and efficiently. 

A recommended plumbing layout for a heater-solar 
combination heating system for a pool / spa combination 
is shown below (

Figure 14

). Your system may not contain 

all of these components, but the basic plumbing will apply 
by eliminating the component in the illustration that is not a 
part of your system.

Note:

 Water temperatures produced by supplemental 

heating sources, such as solar, are not regulated or 
controlled by the heater and may exceed the maximum 
temperature allowed.

 

FILTER

S

A

SPA

INTAKE

POOL

INTAKE

SPA

RETURN

POOL

RETURN

CHECK 

VALVE

FROM SOLAR

TO SOLAR

PUMP

POOL 
DRAIN

SPA
DRAIN

CHECK 

VALVE

SPA 
MAKE-UP

Figure 14

Heater-Solar Layout

Water Pressure Switch Adjustment

The pressure switch is preset at the factory for activation 
at  6  psi  [41.4  kPa]. This  factory  setting  works  for  most 
basic installations. Only adjust the water pressure switch 
if the heater does not operate 

when the proper flow is 

applied  to  unit 

or  if  the  heater  does  not  shut  off  when 

the  filter  pump  is  off.  Occasionally,  unusual  plumbing 
configurations or necessary restrictions in the plumbing 
may  cause  pressure  sensing  problems.  In  these  rare 
situations, the plumbing system configuration may require 
adjustment of the water pressure switch.

Adjustment of the pressure switch may be necessary if any 
part  of  the  filter  system  piping  is  3  feet  [0.91  m]  or  more 
above the top of the heater.

In general, if the heater is installed more than 6 feet [1.83 m] 
below the pool surface, an external water flow switch must 
be added to the plumbing system.

On some installations, the piping from the heater to the pool 
is very short. The back pressure could be too low to trigger 
the  pressure  switch.  If  this  happens,  install  a  directional 
fitting or elbow where the return line enters the pool. This 
will increase back pressure for the heater to operate properly. 
Be sure to check that the system flow is above the minimum 
requirement of 30 gpm (110 lpm) after the directional fitting 
installation.

Be sure the pool filter is clean before making any pressure 
switch adjustment: A dirty filter will restrict the water flow and 
the pressure switch cannot be adjusted properly.

To adjust the pressure switch:

The following adjustment is for installations where the 
heater is 

below

 pool water level.

1.  Be sure that all valves in the system are set to allow 

water flow through the heater. Start the filter pump.

2.  Set the heater temperature above the actual temperature 

to call for heat. Turn the heater ON.

3.  Once the heater is running, turn off the filter pump. The 

heater should turn off immediately.

4.  If the heater continues to operate when the filter pump is 

off, then the water pressure switch needs to be adjusted.

5.  Remove  the  heater’s  left  front  panel  and  remove 

remaining right front panel. The water pressure switch 
is located in the water plumbing in the lower corner of 
the heater.

6.  Slowly rotate the adjustment wheel on the water pressure 

switch in a counterclockwise direction until the “LOW 
WATER  FLOW”  Alarm  shows  on  the  LCD,  the  red 
SERVICE  light  turns  ON,  and  the  heater  stops.  See 

Figure 15

.

The water pressure switch should be adjusted to turn 
the heater off when the pump is off. Setting the switch 

to close at too low of a flow can damage the appliance. Adjust the switch to 
turn the heater off, not on.

A reference scale is on
the back of pressure switch

Turn star wheel 

clockwise 

to

 

raise

pressure set point

Turn star wheel 

counterclockwise 

to 

lower pressure set point

Water Pressure

Switch 

Star Wheel

Figure 15

Содержание ULTRATEMP ETi 220

Страница 1: ...ENGLISH INSTALLATION AND USER S GUIDE HYBRID HEATER IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS ULTRATEMP ETi ESPA OL FRAN AIS ENGLISH...

Страница 2: ...to EasyTouch via Heater Spade Terminals Connecting to EasyTouch via RS 485 Connector Pin Configuration for Heater Control Board to EasyTouch Connecting EasyTouch to the Heater Operating the Heater Swi...

Страница 3: ...the 100 F 38 C maximum rule 4 Before entering the spa or hot tub the user should check the water temperature with an accurate thermometer Spa or hot tub thermostats may err in regulating water temper...

Страница 4: ...rbon monoxide detectors must be periodically inspected for proper operation so as to insure continued safety Broken or malfunctioning carbon monoxide detectors must be replaced immediately This heater...

Страница 5: ...ral purpose water heater 4 The heater should be located in an area where leakage of the heater or connections will not result in damage to the area adjacent to the heater or to the structure When such...

Страница 6: ...acket 4 Electric cutout switch that will interrupt all power to the unit This switch must be within line of sight of the heater Check local codes for requirements 5 Watertight conduit to run the elect...

Страница 7: ...oth the plumbing and control panel side of the heater This will provide necessary room for servicing 2 At least 12 inches 305 mm of clearance must be available on all the other sides of the heater to...

Страница 8: ...SIDE VIEW Building From building wall Exhaust Grill Vent 12 30 5cm Roof Overhang 4 1 2m 4 1 2m 12 30 5cm Must be at least 3 ft 0 9 m above any forced air inlet located within a 10 ft 3 5 m radius Vent...

Страница 9: ...r drains and or pipes particularly those that are metal Ensure that the drain drainpipe and anything that will come in contact with the condensate can withstand the acidity Damage caused by failure to...

Страница 10: ...location on the equipment pad 2 Place the clamps at the base of the heater in the eight 8 locations shown in Figure 5 Note Bolts and washers are not included with the heater The installer must provid...

Страница 11: ...Install a chemical resistant one way check valve between the heater and the chemical feeder to prevent back siphoning through the heater when the pump is off Note If the heater is plumbed in backward...

Страница 12: ...ressure Relief Valve Kit P N 475943 complying with the ANSI ASME Boiler and Pressure Vessel Code having a capacity equal to the Btu hr rating of the heater Note The relief pressure of the valve MUST N...

Страница 13: ...um 3 PVC Pipe 2 PVC Pipe Flow Meter To Pool 3 Ball Valve Bypass Check Valves are optional on heater inlets but will help for system balancing 36 914 mm 2 PVC Pipe 2 PVC Pipe 2 PVC Pipe 3 PVC Pipe 3 PV...

Страница 14: ...e plumbing system On some installations the piping from the heater to the pool is very short The back pressure could be too low to trigger the pressure switch If this happens install a directional fit...

Страница 15: ...ipe as this may cause damage to the gas valve which may result in heater failure The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that...

Страница 16: ...lve Risk of explosion if a unit burning propane gas is installed in a pit or other low spot Propane is heavier than air Do not install the heater using propane in pits or other locations where gas mig...

Страница 17: ...Remove the long side service panel of the heater cabinet There is no need to remove the star head screws 2 Remove the short side service panel to the heater electrical compartment 3 Remove the sheet m...

Страница 18: ...14 ULTRATEMP ETI Hybrid Heater Installation and User s Guide Wiring Diagram Input Side...

Страница 19: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 15 Wiring Diagram Output Side P N 476088 B 4 10 18 ENGLISH...

Страница 20: ...s 1 Turn off the power to both the remote pool spa control system and the heater 2 Remove the side panel of the heater cabinet you do not need to remove the star head screw at the top left corner 3 Re...

Страница 21: ...Run a UL approved conductor cable from the heater to the Load Center 5 Route the cable up through the low voltage raceway located on the left of the Load Center to the Personality Board see image belo...

Страница 22: ...tem power before making any connections 2 Unlatch the EasyTouch load center front door spring latches and open the front door 3 Remove the cover panel screws securing the high voltage cover panel and...

Страница 23: ...ace the side panel 8 Restore power to the heater and the EasyTouch control system 9 Press the MENU SELECT button to scroll to the Remote Mode screen Toggle the selection by pressing one of the arrows...

Страница 24: ...he cost of operating your heater without sacrificing performance 1 The American Red Cross recommends a maximum water temperature of 83 86 F 28 3 30 C Use an accurate pool thermometer A difference of 3...

Страница 25: ...ore details and explanations regarding heater features and programming Pre Startup 1 This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner D...

Страница 26: ...bout 15 seconds the burner should fire When operating for the first time the burner may not fire on the first try because of air in the gas line If it does not fire at first push the ON OFF button wai...

Страница 27: ...e water pressure switch refer back to page 10 Water Pressure Switch Adjustment Turn the star wheel on the switch clockwise to raise setting heater below the pool level and counterclockwise to lower th...

Страница 28: ...loat Switch CFS The Float Switch CFS is a sensing application that shuts down the heater once the condensate level exceeds the permitted level in the condensate container Ignition Module Operation The...

Страница 29: ...an RS 485 connected IntelliFlo pump when the heater is attempting to heat to its set point Suction Temperature Screen Shows the suction line temperature of the refrigerant This screen only appears if...

Страница 30: ...T ___ Remote Mode Relay In Relay Remote Mode operation the heater is started and stopped by remote relays which are connected to the remote POOL COMMON and SPA quick connect terminals on the back of t...

Страница 31: ...h an RS 485 connected IntelliFlo or IntelliPro pump to ensure water is flowing through the heater when water heating is required Note This feature requires that an RS 485 communication cable be connec...

Страница 32: ...message for two 2 minutes FIVE ALARMS Indicates that five 5 faults have occurred in one 1 hour This fault will automatically reset in one 1 hour or can be manually reset by pressing the ON OFF button...

Страница 33: ...using the UP and DOWN arrows Defrost Screen Allows the user to Enable Disable Defrost feature Heat Pump Input Screen and Output Screen Diagnostic displays showing the status of the input sensors and...

Страница 34: ...e the heater compressor stops The heater evaporator fan will continue to run and will draw air over the evaporator fins for about 15 minutes If the refrigerant sensor detects a temperature above the d...

Страница 35: ...NTY CYCLES number of cycles over the lifespan of the unit Press the UP and DOWN arrows to scroll through the Timers and Counters The last screen provides an option to reset the Run Time Log Time and C...

Страница 36: ...of your pool water is available from your local pool supply store If pH becomes too high over alkaline it has these effects 1 Reduces the ability of chlorine to destroy bacteria and algae 2 Water beco...

Страница 37: ...e the heat pump is in operation The heater base is designed to allow the condensation to exit through the bottom drain port when the unit is running The condensation will increase as the outdoor air h...

Страница 38: ...to partially drain then reassemble 8 Use a blower connected to the outlet of the heater to remove all remaining water from the heater 9 Cover air inlet grate with a plastic bag to prevent bugs leaves...

Страница 39: ...80W Current Amp 80A 63RH 80W Capacity Btu h 50A 63RH 80W COP 50A 63RH 80W Power Input KW 50A 63RH 80W Current Amp 50A 63RH 80W Min Circuit Ampacity Amp 148 4 150 Electrical Supply Voltage Requirement...

Страница 40: ...s closely matched by the ambient and water flow conditions 0 1 2 3 4 5 6 7 8 9 10 11 12 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure Drop psi Water Flow gpm UltraTemp ETI Pressure Drop Curve Pres...

Страница 41: ...If shows open replace thermistor If good replace control board SUCTION TH SHORT Alarm Defrost refrigerant temperature sensor circuit is shorted Bad thermistor or bad control board Use the 10k ohm resi...

Страница 42: ...ed Call for professional servicing LOW REFRIG Alarm Refrigerant low pressure switch is open 1 Low refrigerant in system Call for professional servicing 2 Air and water temperatures too cold to operate...

Страница 43: ...nector pin 1 and ignition control module terminal F2 On call for heat if blower starts but shuts off within 30 seconds refer to Faulty Air Flow Switch or Switch Wiring troubleshooting below 6 Faulty a...

Страница 44: ...ore attempting to Troubleshoot Electrical Box 1 Heater condensate drain hose restriction Verify proper hose routing from heater base Ensure there are no loops kinks or elevated portions between hose e...

Страница 45: ...heater Unit ON and Set Temperature is above Actual but Unit is not heating No Alarms Heater is in the five minute safety delay and Compressor has not started Faulty Compressor Faulty Capacitor Compre...

Страница 46: ...ue Contact certified electrician BURNER TROUBLESHOOTING Loud high pitched whine Flame is too rich Verify pressure tap between gas valve and blower inlet See page 11 and verify that the gas regulator s...

Страница 47: ...ULTRATEMP ETI Hybrid Heater Installation and User s Guide 43 REPLACEMENT PARTS Heater Parts Breakdown REFRIGERATION OUTER SHELL p 44 GAS SYSTEM p 45 ELECTRICAL p 46 PLUMBING p 47 ENGLISH...

Страница 48: ...ck 9 475230Z Compressor Blanket 10 475948Z Titanium Heat Exchanger Tie Down Bracket 11 475949Z Titanium Heat Exchanger 12 473735Z Compressor ZP70 Item Part Description 13 473121 Drier Single Direction...

Страница 49: ...st Replacement Kit 25 475877 Exhaust Gasket Kit 2 Pieces 26 475989 Gas Engine Spark Electrodes 27 475898 Burner Assembly 28 462023 Flame Sensor Item Part Description 29 475897Z Heat Exchanger 100K BTU...

Страница 50: ...Wire Harness Heat Pump Inputs 35 475930Z Wire Harness Outputs 36 475926Z Wire Harness Spark Plugs 37 475931Z Wire Harness Gas Blower 38 473155 Transformer 39 475933Z Ignition Control Module Item Part...

Страница 51: ...75941 Switch Automatic Gas Shutoff 140 F 56 475955Z Switch High Limit 127 F 57 471566 Probe Thermistor Water Temperature 58 473381 Union PVC 2in 59 475953Z QRC Clip 60 98218900 Drain Plug 1 4 NPT Item...

Страница 52: ...essly noted names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Po...

Отзывы: