Installer manual Fleck 9000 SXT - Programming
Ref. MKT-IM-020 / C - 21.11.2019
61 / 118
6.5.15
Meter pulse
Set the meter pulse for a non-standard flow meter.
Info
The meter pulse parameter is only available if the Gen option has been set in flow
meter type selection.
1. Press
or
to set the meter constant in pulses per unit
of volume.
2. Press
to validate the selection and to exit the master
programming mode.
6.6
Diagnostic
6.6.1
Peak flow rate (PF)
Info
The controller registers the highest flow rate (L/min) since the last regeneration.
1. Peak flow rate display:
6.6.2
Commands
Info
If none of the buttons are pushed for 1 minute in the diagnostic mode the controller
returns to Service mode.
1. Press and hold
and
for five seconds to enter the diagnostic mode.
2. Press
or
to navigate in the diagnostic mode.
3. Press
to exit the Diagnostic mode at any time.
6.6.3
Current flow rate (FR)
Info
The display is updated every second.
1. Current flow rate display (L/min or gpm depending on display
format programmed):
Содержание FLECK 9000 SXT
Страница 1: ...FLECK 9000 SXT INSTALLER MANUAL WATER PURIFICATION...
Страница 20: ...Installer manual Fleck 9000 SXT Description 20 118 Ref MKT IM 020 C 21 11 2019 3 4 Outline drawing...
Страница 78: ...Installer manual Fleck 9000 SXT Maintenance 78 118 Ref MKT IM 020 C 21 11 2019...
Страница 80: ...Installer manual Fleck 9000 SXT Maintenance 80 118 Ref MKT IM 020 C 21 11 2019...
Страница 82: ...Installer manual Fleck 9000 SXT Maintenance 82 118 Ref MKT IM 020 C 21 11 2019...
Страница 85: ...Installer manual Fleck 9000 SXT Maintenance Ref MKT IM 020 C 21 11 2019 85 118...
Страница 87: ...Installer manual Fleck 9000 SXT Maintenance Ref MKT IM 020 C 21 11 2019 87 118...
Страница 89: ...Installer manual Fleck 9000 SXT Maintenance Ref MKT IM 020 C 21 11 2019 89 118...
Страница 92: ...Installer manual Fleck 9000 SXT Maintenance 92 118 Ref MKT IM 020 C 21 11 2019...
Страница 118: ...www pentairaquaeurope com...