51
Biffi
ICON 2000
InstructIon and operatIng manual
12.11 diaGnostic MessaGes
The alarm and warning lists contain the alarms
and warnings momentarily present�
warning
is the condition that occurs when a
variable reaches a critical value and/or when a
maintenance action is required but all actuator
functions are still available� The flashing of
the alarm/warning LED indicates a warning
condition�
View procedure
• Move the 3-position selector to either OFF or
REMOTE, then press NO to scroll the list of
available variables�
• Press YES when the display shows message
“ALARMS view?” Press yES to scroll the list
of alarms�
• Press NO when the display shows message
“ALARMS view?”�
• Press YES when the display shows message
“WARNINGS view?” Press yES to scroll the
list of warnings�
• Press YES to reset the alarms or warnings
with memory�
XXXXXX XXXXXX
XXXXXX NEXT?
ALARMS
VIEW?
ALARM I-I I
NEXT?
ALARM I-I N
NEXT?
RESET
OK?
RESET
OK?
WARNING I-I N
NEXT?
WARNING I-I 1
NEXT?
WARNINGS
VIEW?
display
3-position
selector
local
reMote
yES
yES
yES
yES
yES
yES
yES
yES
yES
yES
NO
NO
NO
NO
NO
NO
NO
NO
off
VIEW
VARIABLES
alarm
is the condition that occurs when a
variable is outside the acceptable range and
some actuator function is not available� If the
alarm/warning LED is on there is an alarm
condition�
When the fault condition disappears, the
corresponding alarm or warning also
disappears from the list�
a reset routine
is provided to clear the types
of alarms and warnings that are memorized
(over-torque, jammed valve, etc�)�