![Pentair Biffi ICON 2000 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/pentair/biffi-icon-2000/biffi-icon-2000_instructions-and-operating-manual_1524512035.webp)
35
Biffi
ICON 2000
InstructIon and operatIng manual
Motor
Start
position %
Stop
position %
On time
On time
On time
Off
time
Off
time
Off
time
Start position and stop position may be adjusted
from 0% - 100% separately in opening and
closing direction�
ON time and Off time may be adjusted from
1 sec - 200 sec separately in opening and
closing direction�
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language and then enter the password
according to the instructions (see “Entering
the set-up mode”)� When the message
displayed is “SET-UP MODE OK?” press
yES� Press yES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press yES to select
2-speed timer�
• Press YES to change close direction
parameters, press NO and then yES to
change only open direction parameters�
closing direction
• Press YES if the status is OK, or NO
to change� Press yES to confirm
(status = On, enables 2-speed timer operation
in closing direction status = Off, disables
timer operation in closing direction)�
• Press YES if the position value where pulsing
control starts is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
• Press YES if the position value where pulsing
control stops is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
• Press YES if the value of the ON time of
pulsing control is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
• Press YES if the value of the OFF time of
pulsing control is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
opening direction
• Press YES if the status is OK, or NO to
change� Press yES to confirm (status = On
enables 2-speed timer operation in opening
direction status = Off, disables timer
operation in opening direction)�
• Press YES if the position value where pulsing
control starts is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
9.1.11 2-speed timer
The “2-speed timer” routine is used to extend
the actuator travelling time in opening and/or
closing direction, by driving the motor by
pulses which duration (ON and Off time) is
configurable� Pulsing control can be applied to
full travel or only a part of it�
• Press YES if the position value where pulsing
control stops is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
• Press YES if the value of the ON time of
pulsing control is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
• Press YES if the value of the OFF time of
pulsing control is correct, press NO to scroll
the list of available values� Press yES when
the value is correct�
9.1.12 Bus (or fdi control)
This routine is only available if a fieldbus
interface card is present� The routine allows
setting the most important parameters
(node address, termination, etc�) necessary
to connect the actuator to a fieldbus� If the
ICON 2000 was set to work with fieldbus, but
the fieldbus card is not present, a Hardware
alarm will be generated� Different interfaces
are available to connect the ICON 2000 to
different types of fieldbus� If the bus interface
is LonWorks, the routine “BuS” changes in
“fDI control”� See the specific manuals for
instruction and setting of the above modules�
9.1.13 Miscellaneous
It includes different types of routines as “time
and date”, “factory settings”, “lithium battery”,
“torque profile”, etc� used only for special
application or in particular conditions�
9.1.13.1 time and date
Time and date are used in maintenance
functions to associate the time information to
the memorized event (torque profile, alarm
log, maintenance request, etc�)� Time and date
are entered at the time of manufacture, but
they can be adjusted during commissioning or
maintenance operations�
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP�
Select the language and enter the password
according to the instructions (see “Entering
the set-up mode”)� When the message
displayed is “SET-UP MODE OK?” press
yES� Press yES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press yES to select
Miscellaneous�
• Press YES to enter the time and date routine.
• Press YES if the time is correct, press NO to
change it�
• Enter hours, minutes and seconds. Press NO
to scroll the list of available values, press yES
to select�
• Press YES when the time is correct.
• Press YES if the date is correct, press NO to
change�
• Enter day, month, and year. Press NO to
scroll the list of available values, press yES to
select�
• Press YES if the date is correct.