Biffi
ICON 2000
InstructIon and operatIng manual
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language and then enter the password
according to the instructions (see “Entering
the set-up mode”)� When the message
displayed is “SET-UP MODE OK?” press
yES� Press yES to select the actuator set-up
menu, press NO to scroll the list of available
routines and then press yES to select Local
controls�
• Press YES to change control mode, or press
NO to proceed to LED’s color setting�
control mode
• Press YES if the display shows the correct
control mode or press NO to scroll the list
of available options (push-to-run, latched)�
Press yES to confirm�
Option "push-to-run rel� AS5-6" is used when
a remote enabling of local commands is
required� With the local selector in LOCAL,
pressing the OPEN or CLOSE local push-
buttons causes relays AS5 or AS6 to switch,
but no command is sent to motor� The
control PLC should read the status of the
above-mentioned relays and send an open
or close command on the remote inputs
(see paragraph 5�6, push-to-run mode; see
relevant electrical diagram when the option is
used)�
led’s color
• Press YES if the color of the open LED is
correct� Press NO to change it, then yES to
confirm�
• Press YES if the color of the close LED is
correct� Press NO to change it, then yES to
confirm�
• Press YES if the color of the alarm LED is
correct� Press NO to change it, then yES to
confirm�
9.1.6 output relays
Monitor relay
The voltage-free, change-over, contacts of the
monitor relay indicate that the actuator is either
available for remote control or that a problem
or a condition preventing remote control of the
valve exists�
The following situation can be configured
individually to switch-over the monitor relay:
- motor over-temperature
- over-torque
- jammed valve
- LOCAL/Off selected
- manual operation
- ESD signal on (ESD-EfS)
- low lithium battery (if present)
- LOCAL/STOP pressed
The contacts may be configured to make
or break on condition� The options “EfS in
manual”, “EfS mid-travel” and “PST failed”
also appear in the menu, but are not available
for ICON 2000 v4�
status
- open limit
- closed limit
- position >= xx %
- position <= xx %
- closing
- opening
- motor running
- blinker
- mid-travel position
- local selected
- remote selected
- local stop active
- ESD signal on
- manual operation
alarm
- motor over-temperature
- over-torque
- over-torque in OP
- over-torque in CL
- valve jammed
- warnings
- valve jammed in OP
- valve jammed in CL
- low lithium battery (if present)
- mid travel alarm in CL/OP
- mains-only AS8
auxiliary output relays
for status indication or diagnostic purposes,
8 voltage-free contacts of 8 relays are available
to be configured individually to switch for the
following conditions:
9.1.5 local controls
This routine allows:
- To configure the control mode by means
of the local controls when the 3-position
selector is in LOCAL� The available options
are “push-to-run”, “latched”, “latched with
instant reverse”�
- To set the LED’s color� The following options
are available: open LED: green or red; close
LED: green or red; alarm LED: yellow or red�
The monitor relay is normally energized and
will be de-energized on:
- main voltage failure
- lost phase
- internal temperature alarm
- K1 contactor failure
- K2 contactor failure
- position sensor failure
- speed sensor failure
- configuration error
- HW error
- mid-travel alarm
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP�
Select the language and enter the password
according to the instructions (see “Entering
the set-up mode”)� When the message
displayed is “SET-UP MODE OK?” press
yES� Press yES to select actuator set-up
menu, press NO to scroll the list of available
routines and then press yES to select Output
relays�
• Press YES to select DEFAULT #1, or press
NO to change�
• Press YES to select DEFAULT #2, or press
NO to configure the output relays�