12� TROuBLESHOOTING
The ICON 2000 actuator has passed the
functional test performed by Biffi Quality
Assurance personnel�
warninG
The actuator is non-intrusive. The control
compartment was sealed in dry and clean
conditions and contains no site serviceable
components. Do not open it unless absolutely
necessary. Unauthorized access will invalidate the
warranty.
warninG
Since the control compartment contains a
3.6V lithium battery, only open it in safe area. If
the actuator is located in a hazardous area, a
“hot work” permit must be obtained unless the
actuator can be moved to a non-hazardous area.
If the actuator does not work, before
troubleshooting make sure that:
• the numeric display indicates xx %;
• the local selector is not in OFF;
• the main supply voltage is the same as stated
in the name plate menu;
• you move the local selector to OFF and check
that the alphanumeric display shows one of
the following messages:
- “normal
off”
- “alarm
off”
- “warning
off”
- “ESD ON
off”
- “INT
off”
If the above checks are satisfactory try to locate
the fault using the diagnostic facilities�
12.1 the electronics do not switch on
when powered
• Check that the value of the main voltage on
terminals L1, L2, L3 is correct�
• Remove the cover of the compartment where
the electronic cards are located�
• Check the fuse mounted on the power card.
Replace it if burnt�
• If the fuse is OK, check the wires between
terminals L1, L2, L3 and connector M1 of
the power card� If it is correct, replace the
power card�
12.2 dc output VoltaGe not aVailaBle
at the terMinals
• Switch the main power supply off and
disconnect all wires from terminals B1-B2
and C1�
• Switch the main power supply on and check if
the voltage on the terminals B1-B2 and C1 is
between 23 and 27 V DC�
• If the voltage is correct check the external
wiring and the electrical load� It should not
exceed 4 W�
• If the voltage is not correct replace the
power card�
1� Power card
2� fuse
12.3 the actuator does not work froM
reMote controls
• Move the 3-position selector to LOCAL and
check that the actuator works from local
controls�
• Move the local selector to REMOTE. If the
ESD signal is active, the alphanumeric
display indicates “ESD On”� Check the signal
on terminals C3 and C4 and adjust the ESD
configuration� If the alphanumeric display
indicates “INT”, an interlock control is
present� Check the signal on terminals B3, B4
and B5, and adjust Interlocks configuration�
• Check that:
- the wiring to terminals B1-B2 and C1 is
correct;
- there is no short-circuit between wires;
- the electrical load does not exceed 4 W;
- the value is in the range 20-120 V AC
50/60 Hz or 20-125 V DC, if external voltage
supply is used�
12.4 the Motor is Very hot and does
not start
• Check that no alarm other than motor
overheating is present�
• Wait until the motor cools down and the
normally closed contact of the thermal switch
automatically resets before trying to operate
the actuator again�
• Check that the number of operations per hour
and their duration is suitable for the actuator
service (see the name-plate menu)�
• Check that the valve operating torque is
within the range of the unit’s designed
operating torque�
• Always check the causes of abnormal
operation�