9.1.9 out 4-20 ma
This routine is only available if the Ain/Aout
card is present� With this card the ICON 2000
is provided with a 4-20 mA analog input and a
4-20 mA analog output�
The 4-20 mA output can be configured to
provide a current proportional to either
“position” or “torque”� The polarity option
allows to reverse the relationship between the
present position or torque and the 4-20 mA
output signal, according to the following
diagrams:
output: position
polarity: 4 ma = cl
Output mA
20 mA
4 mA
Position %
0% 100%
20 mA
4 mA
output: position
polarity: 4 ma = op
Output mA
Position %
0% 100%
output: torque
polarity: 4 ma = cl
output: torque
polarity: 4 ma = op
Output mA
Output mA
20 mA
12 mA
12 mA
4 mA
20 mA
4 mA
Torque %
Torque %
100% CL 0% 100% OP
100% CL 0% 100% OP
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language and then enter the password
according to the instructions (see “entering
the set-up mode”)� When the message of
the display is “SET-UP MODE OK?” press
yES� Press yES to select the actuator set-up
menu, press NO to scroll the list of available
routines and then press yES to select
Out 4-20 mA�
• Press YES if the output is correct (POSITION
or TORQuE), or press NO to change it, then
press yES�
• Press YES if the polarity is correct, or press
NO to change it, then press yES�
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language and then enter the password
according to the instructions (see entering the
set-up mode)� When the message displayed
is “SET-UP MODE OK?” press YES. Press YES
to select the actuator set-up menu, press NO
to scroll the list of available routines and then
press yES to select fAIL SAfE�
• Press YES if the configured ACTION is correct
(open, close, stay-put, go to position xxx%,
off), or press NO to change it, then press yES�
• Press YES if the configured value of the
DELAy is correct (from 0 to 255 sec), or press
NO to change it, then press yES�
9.1.10 interlock
The interlock inputs can be used to inhibit the
actuator movement in open or close direction�
The controls are momentary, the inhibit
action continues until the relevant signal is
present� The interlock controls work when the
local selector is in LOCAL or in REMOTE� The
ESD control overrides the interlock controls�
The following options can be configured:
-
Interlock OP:
active when signal is PRESENT, active when
signal is ABSENT, no action (Off)�
-
Interlock CL:
active when signal is PRESENT, active when
signal is ABSENT, no action (Off)�
configuration procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language and then enter the password
according to the instructions (see entering the
set-up mode)� When the message displayed
is “SET-UP MODE OK?” press YES. Press YES
to select the actuator set-up menu, press NO
to scroll the list of available routines and then
press YES to select INTERLOCK.
• Press YES if the configured value of the
Open Interlock is correct (PRESENT,
ABSENT, Off), or press NO to change it, then
press yES�
• Press YES if the configured value of the
Close Interlock is correct (PRESENT,
ABSENT, Off), or press NO to change it, then
press yES�