77
12.16 - “Users’
menu”
When entering the “Users’ menu”, the
display, item “1” in fi gure 62, will start
blinking indicating that a change of
mode has taken place. To access the
“Users’ menu” (see also section 16 to
better understand the several menus):
press the
button for 2
seconds until the display starts
blinking;
press and release the
button
several times until the desired
parameter is displayed;
use the
or
keys, to
change the value of the selected
parameter.
press
to save the parameter
change before going to the next
parameter.
When the last parameter has been
reached and the
button
pressed, the display will stop blinking
indicating exit from the menu.
12 - USE
Adjustment of the curve angel as shown in
fi gures 63 and 64 when outdoor reset is active
per section 12.9.
Adjustment of the “Minimum heating
temperature” as shown in fi gures 63 and 64
when outdoor reset is active per section 12.9.
Adjustment of the “Maximum heating
temperature” as shown in fi gures 63 and 64
when outdoor reset is active per section 12.9.
Adjustment of the parallel shift of the curve as
shown in fi gures 63 and 64 when outdoor reset
is active per section 12.9.
Display of the calculated heating temperature
when outdoor reset is active per section 12.9,
or display of the temperature set by knob “7”
shown in fi gure 62.
Display of the domestic hot water temperature
when set by knob “11” shown in fi gure 62.
Display of last error code registered, section
12.18.2
Display of last lockout occurred, section 12.18.1
Setting range: 0,1 to 5,0
Setting range: see section 12.10.3
Setting range: see section 12.10.3
The adjustment is made by turning knob “7” shown
in fi gure 62. The selected curve can be shifted up
or down by
18 °F
(10 °C)
.
Temperature display only with a range between 68
°F
(20 °C)
and 189 °F
(87 °C)
.
Temperature display only with a range between 104
°F
(40 °C)
and 158 °F
(70 °C)
, see section 12.7
Error code display per section 12.18.2
Fault code per section 12.18.1
PARAMETER DESCRIPTION
INFORMATION ON DISPLAY ITEM “2” of fi gure 62
NOTE: If no key is pressed for
more than 60 seconds, the control
automatically exits the “Users’
menu”. Any parameter change not
saved using the
button, will
be lost.
The table below lists each “Users’
menu” parameter, what it affects and
its adjustment range.