48
8 - INSTALLATION - Vent & combustion air
Figure 35- Concentric sidewall termination
clearances
8.11 - Sidewall
termination –
Concentric vent
8.11.1 - Description and usage
The termination kit must terminate outside the
structure and must be installed as shown in
Figure 35. The required concentric termination
kit as well as combustion air and vent pipe
materials are listed in Tables 4 and 5.
8.11.2 - Sidewall termination
installation
1. Determine the best location for the
termination kit (see Figure 35).
2. The total length of piping for vent or air
must not exceed the limits given in Section
8.3.
3. You must consider the surroundings when
terminating the vent and air:
a. Position the vent termination where
vapors will not damage nearby shrubs,
plants or air conditioning equipment or
be objectionable.
b. The fl ue products will form a noticeable
plume as they condense in cold air.
Avoid areas where the plume could
obstruct window views.
c. Prevailing winds could cause freezing
of condensate and water/ice buildup
where fl ue products impinge on building
surfaces or plants.
d. Avoid possibility of accidental contact of
fl ue products with people or animals
e. Do not terminate above any door
or window. Condensate can freeze,
causing ice formations.
f. Locate or guard vent to prevent
condensate damage to exterior fi nishes.
4. Cut one (1) hole 5 inch diameter into the
structure to install the termination kit.
5. Install the Concentric vent kit following the
concentric kit manufacturer’s instruction.
NOTICE Ensure termination location
clearance dimensions are as shown in Figure
35.