4.5.7 TOTALIZATION CONFIGURATION
Selection of the totalization funciton, how to reset the totalizer, the decimal position, the low
flow cutoff point, the time base and the functions of the presets are all covered in the Program
mode. Preset values are adjusted in the Preset Adjust mode.
4.5.8 RESETTING THE TOTALIZER
Resetting the Totalizer (to 0) can be accomplished from the keypad or from a remote contact
closure.
Resetting the totalizer from the keypad for Pen 1 is accomplished by selecting the totalizer
display and by depressing the UP key and then also depressing the DISPLAY SELECT key
for 5 seconds. Resetting Pen 2 is accomplished by selecting the totalizer display and by
depressing the DOWN key and then also depressing the DISPLAY SELECT key for 5
seconds.
When the totalizer for Pen 1 is reset, the combined total is also reset.
Note: Remote Resetting of the totalizer will not operate if the unit is in the Off mode.
TABLE 4-1 ENABLE MODE
Press the UP and DOWN keys while in
oPEr
or
oFF
modes. All display lamps will light. After
10 seconds, the lamps will go out and
EnAb
will be displayed. Release the keys and the
display will change to
EtSt
. Press and release the DOWN key and each mode to be enabled/
disabled will be displayed. With the Enable mode prompt for the desired mode displayed,
press the SCROLL key to verify that the displayed mode is either
on
(enabled) or
oFF
(disabled). Press the DOWN key to turn off the mode, press the UP key to turn on the mode
or press the SCROLL key to advance the display to the next Enable mode prompt. Use the
"Your Setting" column in the table to record your programming. The Test and Calibration
modes are factory set to
oFF
(disabled).
DISPLAY
AVAILABLE
FACTORY
YOUR
STEP
DESCRIPTION
CODE
SETTINGS
SETTING
SETTING
1
Enable Test Mode
EtSt
on or oFF
oFF
2
Enable Calibration Mode
ECAL
on or oFF
oFF
3
Enable Program Mode
EPro
on or oFF
on
4
Enable Alarm Set Mode
EASt
on or oFF
on
5
Enable Data Logger Setup
EdLS
on or oFF
on
6
Enable Data Logger Display
EdLd
on or oFF
on
7
Enable Preset Adjust Mode
EPSA
on or oFF
on